8 Additional information
BU 0135 en-4118
109
Limit class in accordance with EN 55011
B
A
Operation permissible in
1. Environment (living environment)
X
-
2. Environment (industrial environment)
X
X
1)
Note required in accordance with EN-61800-3
-
2)
Sales channel
Generally available Limited availability
EMC situation
No requirements
Installation and start-up by EMC expert
1)
Device used neither as a plug-in device nor in moving equipment
2)
"The drive system is not intended for use in a public low-voltage network that feeds residential areas".
Table 14: EMC - Limit class in accordance with EN 55011
8.1.3 EMC of device
NOTICE
EMC Interference to the environment
This device produces high frequency interference, which may make additional suppression measures necessary
in domestic environments (
Section 8.1.3 "EMC of device").
The use of shielded motor cables is essential in order to maintain the specified radio interference suppression
level.
The device is exclusively intended for commercial use. It is therefore not subject to the requirements
of the standard EN 61000-3-2 for radiation of harmonics.
The limit value classes are only achieved if
• the wiring is EMC-compliant
• the length of shielded motor cable does not exceed the permissible limits
The shielding of the motor cable must be attached at both sides in the motor terminal box and the
housing of the device in the event of wall mounting.
Device type
Max. motor cable, shielded
Conducted emissions 150 kHz - 30 MHz
Class A
Class B
Device motor-mounted
+
+
Device wall-mounted
100 m
10 m
Summary of Contents for NORDAC START Series
Page 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Page 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Page 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Page 119: ...Key word index BU 0135 en 4118 119...
Page 120: ...6071302 4118...