71
Service Manual – SC500
05 - Control System, Magnetic Smart Key
The following parameters are displayed only when, on reaching the last parameter RESET, the One-Touch
button
is pressed together with the EcoFlex
and vacuum
buttons
If only the One-Touch button
is pressed, the system will return to the first parameter CHM1.
Hidden Parameters
Code
Description
Min.
Value
Factory
Setting
Max.
Value
Meaning
TSERV
Service advisory timer
0
0
1000
Set to a value X greater than 0 if you wish the
“Service Advisory” icon to be displayed every X hours
of machine running time (according to the main
operating time counter). To reset the hour counter
for the icon display countdown (until the next service
advisory), press the BURST and vacuum buttons for
10 seconds with the display on the “SERVICE MENU”
page.
AR
Maximum acceleration ramp (sec.)
0.5 sec.
1.5 sec.
5 sec.
Increase to obtain a less abrupt response when
accelerating, and vice versa.
DR
Maximum deceleration ramp
(sec.)
DISC
0.5 sec.
1.5 sec.
8 sec.
Increase to obtain a less abrupt response when
decelerating, and vice versa.
WARNING: increasing this value increases the
braking distance.
REV
0.5 sec.
2.5 sec.
8 sec.
IR
Maximum deceleration ramp in
reverse (sec.)
0.5 sec.
0.5 sec.
5 sec.
This is the maximum current which can be supplied to
the disc brush deck.
WARNING: increasing this value increases the risk
of the motors overheating.
VS1
Brush 1 motor protection threshold
20A
30A
50A
This is the maximum current which can be supplied to
the disc brush deck.
WARNING: increasing this value increases the risk
of the motors overheating.
VS2
Brush 2 motor protection threshold
20A
40A
50A
This is the maximum current which can be supplied to
the cylindrical brush deck.
WARNING: increasing this value increases the risk
of the motors overheating.
VDEAD
Paddle potentiometer dead zone
0.0V
0.1V
1.0V
Increase if the alarm T3 appears in the rest
position and it is not possible to adjust the system’s
mechanics. (Speed regulation will, however, be more
difficult to modulate)
Continues