SI-INTERBUS User Guide
67
Issue Number: 1
Sa
fety
Introd
Sup
Mec
El
G
A
Non
Vi
S
Contr
Dia
gno
S
F
CM
D tool
Glo
ssa
111
Invalid source
parameter
One or more parameters specified in the IN cyclic data mapping
configuration parameters (Pr
MM.010
to Pr
MM.019
) is outside
of the allowed range for Interbus. The allowed parameter range
is from Pr
0.00
to 199.99.
112
Read mismatch
One or more parameters specified in the IN cyclic data mapping
configuration parameters (Pr
MM.010
to Pr
MM.019
) cannot be
used as a source parameter for IN data. The parameter may
not exist, or is a write-only parameter.
113
Hole in IN data
mapping configuration
IN cyclic data mapping parameters (Pr
MM.010
to Pr
MM.019
)
are not contiguous. It is not possible have an un-used
parameter in the middle of the cyclic data.
115
Inter-option
communications error
A request to set up an inter-option communications read block
failed. Either the server does not support block transfer or
parameters were not legal.
120
Too many IN data
objects mapped
After expanding ranges of block mappings, too many IN cyclic
data channels configured.
121
Mapping over length
Total size of all IN cyclic data mappings has exceeded the total
size of the cyclic data.
122
Register mode objects
exceeded
More than 10 cyclic IN data channels have been selected with
direct data mapping mode.
204
Multiple non-cyclic
mapping error
A non-cyclic data mode has been mapped more than once in
the OUT cyclic data mapping configuration parameters
(Pr
MM.020
to Pr
MM.029
).
210
Configuration
read error
An error has occurred reading the OUT cyclic data mapping
configuration parameters (Pr
MM.020
to Pr
MM.029
) from the
drive.
211
Invalid destination
parameter
One or more parameters specified in the OUT cyclic data
mapping configuration parameters (Pr
MM.020
to Pr
MM.029
)
is outside of the allowed range for Interbus. The allowable
parameter range is from Pr
0.00
to Pr
199.99
.
212
Write mismatch
One or more parameters specified in the OUT cyclic data
mapping configuration parameters (Pr
MM.020
to Pr
MM.029
)
cannot be used as a destination parameter for OUT data. The
parameter may not exist, or is a read-only parameter. This error
will also occur if an attempt is made to map OUT data to the
configuration parameters of a fieldbus option in another slot,
unless that fieldbus is configured in register mode, i.e.
Pr
MM.009
= On.
213
Hole in OUT data
mapping configuration
OUT data mapping parameters (Pr
MM.020
to Pr
MM.029
) are
not contiguous. It is not possible have an un-used parameter in
the middle of the cyclic data.
214
Duplicate mapping
error
Two or more OUT cyclic data mapping configuration
parameters (Pr
MM.020
to Pr
MM.029
) have been configured
with the same destination parameter reference.
215
Inter-option
communications error
A request to set up an inter-option communications write block
failed. Either the server does not support block transfer or
parameters were not legal.
220
Too many OUT data
objects mapped
After expanding ranges of block mappings, too many OUT
cyclic data channels configured.
221
Mapping over length
Total size of all OUT cyclic data mappings has exceeded the
total size of the cyclic data.
222
Register mode objects
exceeded
More than 10 cyclic OUT data channels have been selected.
Code
Meaning
Description