30
SI-INTERBUS User Guide
Issue Number: 1
7.3
Module reset
Any changes made to the SI-Interbus configuration parameters will not take effect until
the SI-Interbus has been reset.
To reset the SI-Interbus option module set Pr
MM.032
to On.
When the reset sequence has been completed, Pr
MM.032
will be reset to Off and the
SI-Interbus will re-initialise using the updated configuration.
7.4
Restore saved option parameters
If valid configuration parameters have previously been stored in the SI-Interbus flash
memory (Pr
MM.031
), these values can be restored into the host drive parameters by
setting Pr
MM.033
to On.
When the configuration parameter values have been uploaded to the host drive
SI-Interbus will reset and re-configure using the updated parameter values.
This feature allows a pre-configured SI-Interbus module to be installed into a host drive
without losing the SI-Interbus configuration.
7.5
Reset all option modules
To reset all option modules fitted in the drive:
•
Set Pr
MM.000
to 1070
•
Press the red reset button on the drive or set Pr
10.038
to 100
SI-Interbus Module ID
Pr
MM.032
Default
Off
Type
1-bit
Access
RW
This does not store the drive or option module parameters in the drive or option module,
please refer to
.
NOTE
NOTE
Restore Saved Option Parameters
Pr
MM.033
Default
Off
Type
1-bit
Access
RW
This does not store the drive or option module parameters in the drive or option module,
please refer to
.
NOTE
NOTE