42
SI-INTERBUS User Guide
Issue Number: 1
Request
Data word = 0x1101
Stamp Number = 1
Menu = 1
When the first telegram has been received and processed in the slave node, it is
mirrored in the non-cyclic IN word back to the Interbus master controller. This is the
signal to the master controller program that the first telegram of the message has been
received and understood, the second telegram can now be transmitted.
Response
Data word = 0x1101
Stamp Number = 1
Menu = 1
Telegram 2
The second telegram from the Interbus master controller also indicates a WRITE cycle
but the stamp number is now 2.
The data byte contains the parameter number of the parameter that is to be written to.
Request
Data word = 0x1215
Stamp Number = 2
Parameter = 21
When the second telegram has been received and processed in the slave node, it is
mirrored in the non-cyclic IN word back to the Interbus master controller. This is the
signal to the master controller program that the second telegram of the message has
been received and understood, the third telegram can now be transmitted.
Response
Data word = 0x1215
Stamp Number = 2
Parameter = 21
Bit
b15 to b12
b11 to b8
b7 to b4
b3 to b0
Value
0001
0001
0000
0001
Bit
b15 to b12
b11 to b8
b7 to b4
b3 to b0
Value
0001
0001
0000
0001
Bit
b15 to b12
b11 to b8
b7 to b4
b3 to b0
Value
0001
0010
0001
0101
Bit
b15 to b12
b11 to b8
b7 to b4
b3 to b0
Value
0001
0010
0001
0101