Additional features
7.1
Load module default parameters
If set to “On” when the module is reset (
MM.032
= On), this parameter will cause the
option module to return to its “Out of Box” configuration any settings stored on the
module will be returned to their default values.
7.2
Store option parameters
The SI-Interbus module can save a copy of the setup parameters in its flash memory,
this allows the user, for example, to keep a copy of a working set of parameters in the
module in case the host drive is replaced, or if the user modifies the setup parameters
which may result in the Interbus master being unable to communicate with the
SI-Interbus module.
To store the SI-Interbus configuration parameters in the flash memory:
•
Set Pr
MM.031
to On
•
Set Pr
MM.000
to 1001
•
Press the drive red reset button or set Pr
10.038
to 100
The Interbus communication will stop and the SI-Interbus configuration parameters will
be saved within the SI-Interbus flash memory. The SI-Interbus will then reset and re-
initialise using the configuration parameter values.
Load Module Defaults
Pr
MM.030
Default
Off
Type
1-bit
Access
RW
This action does not save the parameters in the drive, a drive save must be performed
if the parameters are to be saved after loss of power (see
).
NOTE
NOTE
Store Option Parameters
Pr
MM.031
Default
Off
Type
1-bit
Access
RW