SI-INTERBUS User Guide
17
Issue Number: 1
Sa
fety
Introd
Sup
Mec
E
G
A
Non
Vi
S
Contr
Di
S
F
CM
D tool
Glo
ssa
5
Electrical installation
The SI-Interbus has a 9-way male ‘D’ type connector for the Remote Bus IN port and an
8-way RJ45 female connector for the Remote Bus OUT port.
The electrical connections are shown in
Table 5-1 SI-Interbus connections
IN Terminal
9-way ‘D’ male
Colour
PLC
Function
Description
1
Yellow
DO1
Positive Data line output from PLC
2
Grey
DI1
Positive Data line input to PLC
3
Brown
0V ISO IN
Isolated 0V Remote Bus OUT
6
Green
/DO1
Negative Data line output from PLC
7
Pink
/DI1
Negative Data line input to PLC
Shield
Shield
Remote Bus IN cable shield
OUT Terminal
Colour
Function
Description
RJ45
female
9-way ‘D’
female
2
1
Yellow
DO2
Positive Data line output from PLC
1
2
Grey
DI2
Positive Data line input to PLC
3
3
Brown
0V ISO OUT
Isolated 0V Remote Bus IN
7
6
Green
/DO2
Negative Data line output from PLC
8
7
Pink
/DI2
Negative Data line input to PLC
Shield
Shield
Shield
Remote Bus OUT cable shield
The terms IN and OUT refer to the physical cable connections for the SI-Interbus
module, not the PLC data direction.
IN refers to the cable from the PLC to the SI-Interbus module.
OUT refers to the cable from the SI-Interbus module to the next slave device.
Ground tab
Remote Bus IN
Remote Bus OUT
NOTE
NOTE