PRIMARY AND SECONDARY WIRING
CONNECTIONS
1.
As shown in Figure 63, connect a two-pair
twisted shielded communications cable to the
DUAL GATE inputs in each unit. The inputs
are located near the base of the Smart DC
Controller. Be sure to connect the wires in pairs
to the same terminal ports (A-A, B-B, and COM
to COM) on both units. See Table 15.
BI-PARTING GATE SYSTEMS
2.
Attach a ring terminal to the shield wire
and connect it to the Smart DC Controller’s
convenient ground screw. Refer to Figure 63.
NOTICE
Connect the ground shield wire to only one
operator, not both.
Table 15. Primary-Secondary Wiring
Primary
Secondary
A
A
COM
COM
B
B
* Only ground to one unit. Do NOT attach the
shield wire to both units.
Shield wire to Ground*
Figure 63. Primary-Secondary Pair Wiring Connections
EXIT
LOOP
BLOCK
EXIT
IN OBS
LOOP
OUT OBS
LOOP
CENTER
LOOP
SENSOR 1
SENSOR
COM
+ 24 V
EMERG
OPEN
SHOW
LEDs
A
U
SE
R2
COM NO
DC
USER 1
EXIT
LOOP
BLOCK
EXIT
IN OBS
LOOP
OUT OBS
LOOP
CENTER
LOOP
SENSOR
1
SENSOR
COM
+ 24 V
EMERG
OPEN
SHOW
LEDs
A
U
SE
R2
COM NO
DC
USER 1
COM
DUAL GATE
RADIO OPTIONS
A
B
COM OPEN +24
V S1
COM
DUAL GATE
RADIO OPTIONS
A
B
COM OPEN +24
V S1
Shielded cable
(3-wire twisted pair)
Conduit (in the ground)
Shield wire
Note: Do not
connect the
ground shield
wire at both ends.
Ground
Primary
Secondary
NOTICE
Use a 2-pair, twisted, shielded cable with one pair of wires used to connect A-A and B-B terminals
between the two boards. The other pair will connect the Common terminals. The shield should
then be grounded on one end to one of the operators.