NEOMERIS CONTROL DES
Appendix
Build:20211025-094624-9873335NSt
All information and technical data are subject to
change
Page 80
1 Monday
Monday
2 Tuesday
Tuesday
3 Wednesday
Wednesday
4 Thursday
Thursday
5 Friday
Friday
6 Saturday
Saturday
»Contact Type
(Sel.)
NEOMERIS CONTROL DES, Device, Time
Dosing 1, Dosing Valve 1
Kind of contact (pulled/released)
Default:
active=energized
0
active=ener-
gized
-
1
active=not en-
ergized
-
»Contact Type
(Sel.)
NEOMERIS CONTROL DES, Device, System
enable
Kind of contact (used/n.used)
Default:
not occupied=active
0
occupied=ac-
tive
-
1
not occu-
pied=active
-
»Contact Type
(Sel.)
NEOMERIS CONTROL DES, Device, Operat-
ing Signal
Kind of contact (pulled/released)
Default:
active=pulled
0 active=pulled
-
1 active=drop off -
»Range
(Sel.)
NEOMERIS CONTROL DES, Device, Blow-
down Analog Output
Range of current
Default:
4..20 mA
0 0..20 mA
-
1 4..20 mA
-
»Upper Limit
(Num.)
NEOMERIS CONTROL DES, Device, Blow-
down Analog Output
Maximal possible value of the conductivity
Range:
0 ... 5000 µS/cm
Default:
2000 µS/cm
»Lower Limit
(Num.)
NEOMERIS CONTROL DES, Device, Blow-
down Analog Output
Minimal possible value of the conductivity
Range:
0 ... 5000 µS/cm
Default:
0 µS/cm
Switch On Delay
(Num.)
NEOMERIS CONTROL DES, Device, Circula-
tion Pump
Delay of pump start after internal enable
Range:
0 ... 999 s
Default:
15 s
»Contact Type
(Sel.)
NEOMERIS CONTROL DES, Device, Circula-
tion Pump
Kind of contact (energised/off)
Default:
active=energized
0
active=ener-
gized
-