NEOMERIS CONTROL DES
Functional description
Build:20211025-094624-9873335NSt
All information and technical data are subject to
change
Page 41
Range:
0 ... 5000 µS/cm
Default:
50 µS/cm
»Min(Alarm)
(Num.)
Alarm low limit
Range:
0 ... 5000 µS/cm
Default:
25 µS/cm
»Max(Warn.)
(Num.)
Warning high limit
Range:
0 ... 5000 µS/cm
Default:
2800 µS/cm
»Max(Alarm)
(Num.)
Alarm high limit
Range:
0 ... 5000 µS/cm
Default:
3000 µS/cm
»Hysther.(Warn.)
(Num.)
Hysteresis, used as +/- from threshold
Range:
0 ... 5000 µS/cm
Default:
0 µS/cm
»Hysther.(Alarm)
(Num.)
Hysteresis, used as +/- from threshold
Range:
0 ... 5000 µS/cm
Default:
0 µS/cm
»Prio Warn.
(Num.)
Set warning priority
Range:
0 ... 99
Default:
50
»Prio Alarm
(Num.)
Set alarm priority
Range:
0 ... 99
Default:
20
»Delay Warn.
(Num.)
Delay of warning triggering
Range:
0 ... 999 s
Default:
0 s
»Delay Alarm
(Num.)
Delay of alarm triggering
Range:
0 ... 999 s
Default:
0 s
»Reac. Sys.
(Sel.)
Reaction of the system to an alarm-type mes-
sage
Default:
Continue
0 Continue
No shutdown
1 Shutdown Shutdown with permanent retries
2
Cycl.shut-
down
Shutdown with defined number of
retries
3
Dur. shut-
down
Durable shutdown