4.1.7 Analog Inputs
The control unit has the following analogue inputs / measuring inputs:
Identifier
Cond. Probe (conductive)
Information
Type
Conductivity, conductive sensor
Range
0 ... 5000µS/cm
Input Resistance
-
Resolution
0.2%
Accuracy
2%
Linearity
1%
Filter
Tau = 1s
Linearization
Temperature compensation 2.2%/K
Model / Type
for cell constant K=0.01 ... 10
Remark
-
Identifier
Cond. Probe (inductive)
Information
Type
Current Input
Range
0 ... 20mA, 2/3-wire
Input Resistance
175 Ohm
Resolution
10Bit
Accuracy
0.5%
Linearity
0.2%
Filter
-
Linearization
-
Model / Type
-
Remark
-
Identifier
Temperature Sensor
Information
Temperature input, PT100, 0...100°C
Type
Temperature input, PT100, 0...100°C
Range
0 ... 50°C
Input Resistance
-
Resolution
0.1%
Accuracy
2%
Linearity
1%
Filter
Tau = 1s
Linearization
-
Model / Type
PT100
Remark
-
Identifier
unused
Information
Type
Power measuring
Range
0 ... 500A
Input Resistance
-
Resolution
0.5%
Accuracy
2%
Linearity
1%
Filter
-
Linearization
-
Model / Type
ind. transformer
Remark
4% ripple