NEOMERIS CONTROL DES
Appendix
Build:20211025-094624-9873335NSt
All information and technical data are subject to
change
Page 77
»Max(Warn.)
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Range:
0 ... 32767 l/h
Default:
900 l/h
»Max(Alarm)
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Alarm high limit
Range:
0 ... 32767 l/h
Default:
3900 l/h
»Hysther.(Warn.)
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Hysteresis, used as +/- from threshold
Range:
0 ... 32767 l/h
Default:
10 l/h
»Hysther.(Alarm)
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Hysteresis, used as +/- from threshold
Range:
0 ... 32767 l/h
Default:
10 l/h
»Prio Warn.
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Set warning priority
Range:
0 ... 99
Default:
50
»Prio Alarm
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Set alarm priority
Range:
0 ... 99
Default:
20
»Delay Warn.
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Delay of warning triggering
Range:
0 ... 999 s
Default:
0 s
»Delay Alarm
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Delay of alarm triggering
Range:
0 ... 999 s
Default:
0 s
»Reac. Sys.
(Sel.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Reaction of the system to an alarm-type mes-
sage
Default:
Continue
0 Continue
No shutdown
1 Shutdown
Shutdown with permanent re-
tries
2 Cycl.shutdown
Shutdown with defined num-
ber of retries
3 Dur. shutdown Durable shutdown
Mode prop.
(Sel.)
NEOMERIS CONTROL DES, Device, Prop.
dosing 1
Activate the proportional dosage
Default:
ON
0 OFF
Switched Off / Inactive
1 ON
Switched On / Active
Pulse relation
(Num.)
NEOMERIS CONTROL DES, Device, Prop.
dosing 1
Number of output pulses per input pulse
Range:
0.00 ... 99.99
Default:
1.00