![Neomeris CONTROL DES Manual Download Page 47](http://html1.mh-extra.com/html/neomeris/control-des/control-des_manual_719137047.webp)
NEOMERIS CONTROL DES
Functional description
Build:20211025-094624-9873335NSt
All information and technical data are subject to
change
Page 40
6.10
Module: MAbsConductivityCompTemp
6.10.1 Info:
Sensor Conduct.
6.10.2 Comment:
Measures the conductivity of the process water.
Due to the determined temperature of the temperature sensor, a temperature compensation can
take place.
There are three ways to compensate for the conductivity value:
1. Temperature compensated using the connected temperature sensor (calibrate the temperature
sensor!).
2. Fix Compensated to the reference value (25 degrees celsius)
3. Not compensated
Submodules:
MTemperature: Measures the temperature
6.10.3 Internal elements of module:
6.10.3.1 Parameters
»Reference
(Num.)
Reference temperature for compensation
Range:
0.0 ... 99.9 °C
Default:
25.0 °C
»Sensor type
(Sel.)
Type of the connected conductivity sensor
Default:
Conductive
0
Conduc-
tive
Conductive
1 Inductive Inductive
»Amplifying
(Num.)
Amplifying of conductivity measurement signal
Range:
0 ... 100 %
Default:
10 %
»Temp.-Comp.
(Sel.)
Switching temperature compensation
Default:
Temp.Sensor
0 without
no temp. compensation
1
Temp.Sen-
sor
compensation according act. tem-
perature
2 fix value
fix compensation
3 external
compensation according external
temperature sensor
»Min(Warn.)
(Num.)
Warning low limit