NEOMERIS CONTROL DES
Functional description
Build:20211025-094624-9873335NSt
All information and technical data are subject to
change
Page 47
Mesrg. Method
(Sel.)
Measuring method(process controlled,
pulscount or pulslength)
Default:
Counter
0 Automatic
-
1 Counter
-
2
Puls
Length
-
Gate Time
(Num.)
Time periode for counting of impulses
Range:
0 ... 9999999 ms
Default:
1000 ms
Debounce
(Num.)
Stabilisation time of impuls
Range:
0 ... 999 ms
Default:
10 ms
»Min(Warn.)
(Num.)
Warning low limit
Range:
0 ... 32767 l/h
Default:
0 l/h
»Min(Alarm)
(Num.)
Alarm low limit
Range:
0 ... 32767 l/h
Default:
0 l/h
»Max(Warn.)
(Num.)
Warning high limit
Range:
0 ... 32767 l/h
Default:
900 l/h
»Max(Alarm)
(Num.)
Alarm high limit
Range:
0 ... 32767 l/h
Default:
3900 l/h
»Hysther.(Warn.)
(Num.)
Hysteresis, used as +/- from threshold
Range:
0 ... 32767 l/h
Default:
10 l/h
»Hysther.(Alarm)
(Num.)
Hysteresis, used as +/- from threshold
Range:
0 ... 32767 l/h
Default:
10 l/h
»Prio Warn.
(Num.)
Set warning priority
Range:
0 ... 99
Default:
50
»Prio Alarm
(Num.)
Set alarm priority
Range:
0 ... 99
Default:
20
»Delay Warn.
(Num.)
Delay of warning triggering
Range:
0 ... 999 s
Default:
0 s
»Delay Alarm
(Num.)
Delay of alarm triggering