Page 61
The current assignment appears:
The current temperature Act: 24.7 °C is assigned to a converter value of 00583. Press the
é
key
to enter the upper point. (Press
ê
to enter the lower point.)
Change the value with the keys
é
or
ê
, with
Enter
a digit is moved to the right. After entering the
value, exit the mask with
Enter
.
The new assignment Act: 25.4 °C to the converter value 00583 is displayed.
Calibration takes place in the following steps:
1. Specifying a reference value to the sensor. In this case, the value must be able to settle for a
sufficiently long time (until the converter value no longer changes).
2. Press the
é
/
ê
-key to adjust the upper / lower calibration point.
3. Measure the real measured value applied to the sensor (with an external reference measuring
device) and enter it (numerical editing).
4. Press the
Enter
-key to accept the new calibration point - the
M
key is used to cancel the adjust-
ment.