Configuration Procedures
5-12
partition; or click Cancel to skip updating the firmware level, and the cell is not
added to the partition.
6. Repeat steps 2 through 5 until the partition contains all desired cells and each cell is
a member of one partition.
5.3.5.
Specifying Partition Settings
Each partition has unique settings for which you can use the default values or specify
other values, using the following procedure. For more information on the settings, refer
to the
User’s Guide
.
1. Navigate to the settings page of the partition remote console interface.
2. Click the link to display one of the following groups of settings, and select or type
the desired values:
y
Power
-
Power cycle interval
-
Power off cells on the next power down command
-
Power restore policy
o
DC power stays off when AC power is applied to cells in the partition
(default).
o
DC power is turned on when AC power is applied to cells in the
partition.
o
DC power is restored to its previous state before AC power was
removed from the cells in the partition.
-
Number of seconds of delay in restoring DC power when AC power is
applied
y
Boot cell (primary and secondary)
y
General
- Partition
name
-
System GUID (partition-specific)
y
Fault
- Degraded
partition
- Failing
units
y
Customer
data
-
Customer name and ID
-
Customer address: street, city, state or province, postal code, and country