3-4 Setting Up Your Server
SELECTING SERVER SITE
Read the following precautions before selecting a suitable site for your server. The following
describes installation of the server and connections to the server.
CAUTION
Observe the following instructions to use the server safely. Failure to follow
these instructions may cause a fire, personal injury, or property damage. See
pages 1-3 to 1-8 for details.
■
Never attempt to lift the server only by yourself.
■
Do not install the server in any place other than specified.
The following figure illustrates a site suitable for installing the server.
* It is recommended that the server should be used in a room where
temperature is in the range between 15 to 25ºC.
Clean and tidy room
Allow clearance of at least 150 mm in
front of and behind the server.
100 to 120 Vac/200 to 240
Vac parallel bi-polar wall
power outlet with the
ground line.
Room that satisfies the
following conditions: *
<While operating>
Temperature: 10 to 35ºC
Humidity: 20 to 80%
Temperature gradient: ±10ºC/h
Atmosphere: 749 to 1040 hpa
<While halting>
Temperature: –10 to 55ºC
Humidity: 10 to 80%
Temperature gradient: ±15ºC/h
Atmosphere: 749 to 1040 hpa
Close enough to connect the
mouse and the display.
Install the server on
a flat, rigid desk
The server must be
fixed with stabilizers.
Summary of Contents for N8100-1422F
Page 16: ...x This page is intentionally left blank...
Page 161: ...Configuring Your Server 4 93 3 Setting menu for VD 0 is displayed...
Page 238: ...7 12 Maintenance This page is intentionally left blank...
Page 356: ...C 2 IRQ This page is intentionally left blank...
Page 410: ...F 2 Using a Client Computer Which Has a CD Drive This page is intentionally left blank...
Page 414: ...G 4 Product Configuration Record Table This page is intentionally left blank...