Error occurrence conditions and check items
5.17. 18Error
Error
Description
If an error (open: 14
ı
or lower) in the space heating return thermistor is detected
continuously for 3 seconds, the system displays the 18E error message. The boiler
maintains the Safety-Shutdown status, and if the heating temperature is sensed
normally, stops postpurge, and returns to the standby mode.
1. Check if the thermistor is open and if the connector is connected properly.
2. Check if the thermistor is defective.
3. Defective PCB.
18E
Space
heating
return
thermistor
open
Check
items
Is the Return thermistor
normal?
Yes
No
Replace Return thermistor
Resistance between two black wires of CN 13 is from
0.8
to
20
KO
at normal condition.
Check connector
Caution
: Before measuring resistance of the thermistor,
remove the connector form the PCB.
©
Navien
Ameri
c
a
I
n
c
.
20
1
0
CH
series
servi
c
e
Manua
l
Version
1
.0
Summary of Contents for CH-180
Page 2: ......
Page 31: ...29 4 4 Wiring Diagram Navien America Inc 2010 CH series service Manual Version 1 0...
Page 143: ...Navien America Inc 2010 CH series service Manual 141 Version 1 0 9 2 Burner Disassemble G...
Page 146: ...Navien America Inc 2010 CH series service Manual 144 Version 1 0 9 3 Water Way Disassemble...
Page 152: ...Navien America Inc 2010 CH series service Manual 150 Version 1 0 Memo...
Page 153: ...Navien America Inc 2010 CH series service Manual 151 Version 1 0 Memo...
Page 154: ...Navien America Inc 2010 CH series service Manual 152 Version 1 0 Memo...
Page 155: ......