79
Check method
Fault
Possible
Causes
Check method
Air presure
hose error,
venturi
clogged
Air presure
sensor
error
1. The air pressure hose is clogged.
Check if the hose is clogged with water remained from
installation.
2. Check if the venturi (burner) hole is clogged with soot or debris.
Blow air with mouth through the air pressure hose.
3. Check if the air pressure hose is torn.
Increased RPM may cause blowout and noise.
03E can occur due to the same trouble.
Does APS* have nominal
operation voltage?
Yes
No
Replace APS
Check Connector
Is there any output voltage
from APS?
Check the voltage between black and red wire of
CN 6: 4.5-5.5VDC
No
Replace APS
Check the voltage between black and white wire of
CN 6: 0.3-4.0VDC
Yes
*APS: Air Pressure Sensor
Is there any restriction in
airflow?
No
Remove all the restrictions in airflow
around unit and check the vent pipe
Yes
Replace tube
Check vent and connector
©
Navien
Ameri
c
a
I
n
c
.
20
1
0
CH
series
servi
c
e
Manua
l
Version
1
.0
Summary of Contents for CH-180
Page 2: ......
Page 31: ...29 4 4 Wiring Diagram Navien America Inc 2010 CH series service Manual Version 1 0...
Page 143: ...Navien America Inc 2010 CH series service Manual 141 Version 1 0 9 2 Burner Disassemble G...
Page 146: ...Navien America Inc 2010 CH series service Manual 144 Version 1 0 9 3 Water Way Disassemble...
Page 152: ...Navien America Inc 2010 CH series service Manual 150 Version 1 0 Memo...
Page 153: ...Navien America Inc 2010 CH series service Manual 151 Version 1 0 Memo...
Page 154: ...Navien America Inc 2010 CH series service Manual 152 Version 1 0 Memo...
Page 155: ......