38
4.6.6. Fan motor
Navien Part No.
Function
Check Point
NAFA9GSFB002
L
Failure Event
Effects
Error Code
E009, E010, E027
Diagnostic
Color /
Number of wires
1. Black-Red : DC 127 ~ 184 V
2. Black-Yellow : DC 15 V
3. Black-Orange : DC 0~7.5 V
4. Black-White : 0 ~ 6,500 RPM
To provide combustion air into the burner and to exhaust flue gas.
Fan operated with APS or ideal combustion.
1. Fan speed failure: the fan RPM are less than or equal to 400 RPM.
2. The fan assembly screw loosens and/or the fan is disassembled.
3. Connection terminal assembly defectiveness.
1. Unstable combustion condition.
2. Unit vibrating and making a noise.
3. The boiler is not operating.
1. Visual inspection: check the fan connection wire and/or the fan mounting
location.
2. Voltage check: Check range of voltage shown below.
\UY_IOXZ[P
? 3.4" (?
_^P
lssv~
ishjr
vyhunl
~op{l
ylk
©
Navien
Ameri
c
a
I
n
c
.
20
1
0
CH
series
servi
c
e
Manua
l
Version
1
.0
Summary of Contents for CH-180
Page 2: ......
Page 31: ...29 4 4 Wiring Diagram Navien America Inc 2010 CH series service Manual Version 1 0...
Page 143: ...Navien America Inc 2010 CH series service Manual 141 Version 1 0 9 2 Burner Disassemble G...
Page 146: ...Navien America Inc 2010 CH series service Manual 144 Version 1 0 9 3 Water Way Disassemble...
Page 152: ...Navien America Inc 2010 CH series service Manual 150 Version 1 0 Memo...
Page 153: ...Navien America Inc 2010 CH series service Manual 151 Version 1 0 Memo...
Page 154: ...Navien America Inc 2010 CH series service Manual 152 Version 1 0 Memo...
Page 155: ......