Error occurrence conditions and check items
5.22. 28Error
Error
Description
1. Space heating water pressure of 7.3 psi or lower is maintained for over 5
minutes, the system displays 28E (regardless of initial power supply).
2. If the space heating water pressure of 7.3 psi or lower is detected, and becomes
7.3 psi or lower in 2 hours after water refilling, the system displays 28E. (The
error is not displayed until 72 hours is passed after the power is connected
initially.)
1. Check the water pressure sensor.
2. Check if the boiler is installed in a low water pressure area.
28E
Leakage
Check
items
Does the water leak
out of pipe?
No
Yes
No
*AWS: Auto Water Supplement
Check*AWS valve
or connector
Voltage between pin1 and pin3 of CN21 is
120VAC
After press the reset button,
Does water supplement
occurred?
Check into pipe and
pipe assembly
No
Yes
No
Replace main PCB
Yes
Does water supplement
terminated within 5min?
Normal state
Yes
During AWS valve operation,
is the output voltage of AWS
valve normal?
©
Navien
Ameri
c
a
I
n
c
.
20
1
0
CH
series
servi
c
e
Manua
l
Version
1
.0
Summary of Contents for CH-180
Page 2: ......
Page 31: ...29 4 4 Wiring Diagram Navien America Inc 2010 CH series service Manual Version 1 0...
Page 143: ...Navien America Inc 2010 CH series service Manual 141 Version 1 0 9 2 Burner Disassemble G...
Page 146: ...Navien America Inc 2010 CH series service Manual 144 Version 1 0 9 3 Water Way Disassemble...
Page 152: ...Navien America Inc 2010 CH series service Manual 150 Version 1 0 Memo...
Page 153: ...Navien America Inc 2010 CH series service Manual 151 Version 1 0 Memo...
Page 154: ...Navien America Inc 2010 CH series service Manual 152 Version 1 0 Memo...
Page 155: ......