6.2 SEQUENCES OF OPERATION
6.2.1 Heating Cycle
1. When thermostat switch is set to heat, the terminals R&W get connected which will energize the
indoor blower and all the relays for the heating elements immediately.
2.
Relay 1, once energized, turns the first Heating element ON with up to 1 second delay. At the
same time Relay 2 powers the rest of the heating elements with delay range from 1 to 8 seconds
(applicable to 7.5 kW, 10kW, and 15 kW).
3.
When the room thermostat is satisfied, terminal R and W connection opens and de-energizes all the
relays, blower and heating elements immediately.
6.2.2 Cooling Cycle
6.2.3 Continuous Fan Cycle
6.2.4
Performance Specification
1. Room thermostat calls for cooling connecting R to Y terminals.
2. The compressor and condenser fan start immediately on a call for cooling. Air circulating fan also
starts immediately with cooling operation.
3.
When the room thermostat is satisfied, terminal Y on the module is de-energized.
4.
The compressor and condenser fan stop immediately when the thermostat is satisfied.
1. When thermostat switch is set to FAN, the terminals R & G get connected which will energize the
indoor blower to circulate the indoor air.
2. The indoor blower will continue to run until the thermostat setting is changed to different
operational mode.
Model No
.
COOLING
HEATING
BTU/h
EER CFM
240V
208V
KW/h BTU/h KW/h BTU/h
P-E05A-A24A-A
24000
11
800
4.8
16300
3.6
12300
P-E07A-A24A-A
24000
11
800
7.3
24600
5.5
18400
P-E10A-A24A-A
24000
11
800
9.6
32700
7.2
24600
P-E15A-A24A-A
24000
11
800
14.4
49100
10.8
36900
TABLE 5.
CONTINUOUS FAN SPEED TAP SHOULD NOT BE CHANGED FROM FACTORY SETTING.
DO NOT USE COMMON SPEED TAP FOR MULTIPLE FUNCTIONS; IT CAN CAUSE UNIT TO
MALFUNCTION.
IMPORTANT
!
!
Summary of Contents for Condo Pack
Page 58: ...58 IOM IOM W415 2288 08 29 2019 9 3 P E HEATING MODULE...
Page 62: ...62 IOM IOM W415 2288 08 29 2019 44 1...
Page 63: ...63 IOM W415 2288 08 29 2019 44 1...
Page 122: ...58 IOM IOM W415 2288 08 29 19 9 3 MODULE DE CHAUFFAGE LECTRIQUE CONDO PACK P E...
Page 126: ...62 IOM IOM W415 2288 08 29 19 44 1...
Page 127: ...IOM W415 2288 08 29 19 44 1...