![Napoleon Condo Pack Installation And Operating Instructions Manual Download Page 10](http://html1.mh-extra.com/html/napoleon/condo-pack/condo-pack_installation-and-operating-instructions-manual_3307042010.webp)
10
IOM
IOM
W415-2288 / 08.29.2019
This design is certified for thru-the-wall installation only. The interior portions of the unit may be surrounded by
a closet with clearances to combustible material as listed on the nameplate.
Minimum clearances to combustibles derived from factory testing are shown below and also on the
nameplate of the unit:
H3.7. 1
THIS UNIT IS CERTIFIED FOR INSTALLATION ON COMBUSTIBLE FLOORS. THIS SHALL
BE INTERPRETED AS A WOOD FLOOR ONLY.
THE UNIT MUST NOT BE INSTALLED DIRECTLY ON CARPETING, OR OTHER
COMBUSTIBLE MATERIAL EXCEPT WOOD.
INSTALLATION ON COMBUSTIBLE MATERIAL OTHER THAN WOOD CAN RESULT IN FIRE,
CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
THE AREA AROUND THE UNIT MUST BE KEPT CLEAR AND FREE OF ALL
COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS
AND LIQUIDS.
THE HOMEOWNER SHOULD BE CAUTIONED THAT THE CONDO PACK AREA MUST NOT
BE USED AS A CLOSET OR FOR ANY OTHER STORAGE PURPOSE.
WARNING
!
!
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS.
DÉGAGEMENTS MINIMAUX PAR RAPPORT AUX MATÉRIAUX COMBUSTIBLES.
TOP / DESSUS
2 “ (50.8 mm)
PLENUM / PLÉNUM
1 “ (25 mm)
FRONT / AVANT
0**
BACK / ARRIÈRE
0
RIGHT SIDE / CÔTÉ DROIT
0*
LEFT SIDE / CÔTÉ GAUCHE
0
BOTTOM / FOND
0***
FLUE PIPE / TUYAU
0
* RECOMMENDED 2 “ (50.8 mm) CLEARANCE FOR SERVICING
* 2 po MIN. RECOMMANDÉ DE DÉGAGEMENT POUR ENTRETIEN
**
10” (254 mm) RECOMMENDED CLEARANCE FOR SERVICING
**
10 po MIN. RECOMMANDÉ DE DÉGAGEMENT POUR ENTRETIEN
*** CERTIFIED FOR CLOSET INSTALATION ON COMBUSTIBLE FLOORING.
*** CERTIFIÉ POUR L’INSTALLATION DANS UN PLACARD SUR UN PLANCHER COMBUSTIBLE.
TABLE 2.
Summary of Contents for Condo Pack
Page 58: ...58 IOM IOM W415 2288 08 29 2019 9 3 P E HEATING MODULE...
Page 62: ...62 IOM IOM W415 2288 08 29 2019 44 1...
Page 63: ...63 IOM W415 2288 08 29 2019 44 1...
Page 122: ...58 IOM IOM W415 2288 08 29 19 9 3 MODULE DE CHAUFFAGE LECTRIQUE CONDO PACK P E...
Page 126: ...62 IOM IOM W415 2288 08 29 19 44 1...
Page 127: ...IOM W415 2288 08 29 19 44 1...