GEM-P1632 Programming Instructions
L
NAPCO Security Systems
!
Page 6
GEM-RP2ASe2/GEM-K2AS Keypad Easy Program Menu
Enter the Dealer Security Code (default = 456789) for a new panel or enter your custom Dealer Program Code if
programmed. Press the PRIOR/NO button repeatedly until “
TURNON/PROG
” is displayed.
NOTE:
If you pass “
TURNON/
PROG
”, you can scroll back by pressing
B
. Press the NEXT/YES button to enter the Dealer Program Mode. In
each of the following steps, press
R
to jump to the next screen, the NEXT/YES button to go forwards, the
PRIOR/NO button to go backwards,
U
to save and
C
twice to exit at any time.
Total Number of Zones in Area 1
(Appears for New Panel Only)
Directly enter the total number of zones to be programmed for Area 1. Valid entries are from 01 to 32.
Directly enter the total number of zones, including leading zeros. Use number buttons
1
through
9
.
NOTE:
Press
0
for a zero. The system is based on groups of 4 zones each (after the first 8
zones), and will automatically round up to the next group of 4. For example, if you enter 18, it will
automatically convert this to 20 zones. Press
U
to save. Press the NEXT/YES button to proceed.
NOTE:
If you are programming a 2 Area system, enter the total number of zones required for Areas 1 & 2. The Direct Address
Program Mode can then be used to remove zones from Area 1 and place them in Area 2. See Zone Options. If Programming a
Wireless Only system, or using wireless only on Zones 9-32, enter the total number of zones in system. Enter the transmitter points in
the RF Transmitter section of the Easy Menu Driven Programming Mode.
Panel Zone Doubling
(Appears for New Panel Only)
If the total number of zones in Area 1 entered was 16 or greater, press the NEXT/YES button to
effectively double the capacity of the control panel's hard wired zones from 8 to 16. The 16 zones will
remain EOL terminated zones, but will be designated for Normally Closed devices only. The terminal for
Zone 1 will now support Zones 1 and 9 with the use of the supplied EZ Zone Doubling
TM
resistors, E & Z
supplied. (Refer to Wiring Diagram and Installation Instructions). If Panel Zone doubling is not desired,
press the PRIOR/NO button.
Fire Zones in Area 1
(Appears for New Panel Only)
Enter the zone number of any zones which are to be used as Fire Zones (both 2-wire, 4-wire or wireless).
Valid entries are from 01 to 32. Directly enter each zone number, including leading zeros, and press
U
to save, and then repeat for any additional zone(s). Press NEXT/YES button to proceed.
NOTE:
If you are programming a 2 Area system, enter all the zone numbers required for Areas 1 & 2.
The Direct Address Program Mode can then be used to remove zones from Area 1 and place them in
Area 2. See Zone Options.
2-Wire Fire Zones in Area 1
(Appears for New Panel Only)
Enter the zone numbers of any Fire Zones (from previous question) which are to be used with 2-wire
smoke detectors. The only valid entries are 07 and 08. Directly enter each zone number, including
leading zeros. Press
U
to save, and then repeat for any additional zone(s).
NOTE:
Only zones which
have been designated as Fire Zones in the prior question may be programmed as 2 Wire Fire zones.
Press the NEXT/YES button to proceed.
NOTE:
JP3 must be set to “2-WF” position for 2-wire fire zones
(refer to Installation Instructions).
Local or Central Station Reporting System
(Appears for New Panel Only)
Press the NEXT/YES button for all zones to report; press the PRIOR/NO button for no zones to report
(LOCAL SYSTEM).
Exit/Entry Zones in Area 1
(Appears for New Panel Only)
Directly enter the zone number of any zones which are to be used as Exit/Entry zones.
Valid entries are
from 01 to 32.
Directly enter each zone number, including leading zeros.
Use number buttons
1
through
9
.
NOTE:
Press the
0
button for a zero.
Press
U
to save and then repeat for any
additional zone(s).
Press the NEXT/YES button to proceed.
NOTE:
Chime will automatically be programmed for all E/E zones.
If you are programming a 2 Area
system, enter all exit/entry zone numbers required for Areas 1 & 2.
The Direct Address Program Mode
can then be used to remove zone from Area 1 and place them in Area 2.
See Zone Options.
R
COMPUTERIZED SECURITY SYSTEM
ARMED
STATUS
SYSTEM ARMED
01/01/97 12:00AM
1 2
4
3
5 6
7 8 9 0
A
B
C
D
E
F
G
NEXT/YES
PRIOR/NO
AREA
GEMINI
ENT A1
ENT A1
GEM-RP2
A
Se2
/GEM-K2
A
S
--Ea
s
y
Me
nu Dr
iv
en Pr
o
g
ram Mode
(Press YES or NO)
(Direct Entry)
E n t 2 W F
Z n # X X
R e p o r t
a l l Z n
(Direct Entry)
E n t E E 1
Z n # X X
(Direct Entry)
E n t A 1
# Z n X X
(Press YES or NO)
Z n D b l
E n a b l ?
(Direct Entry)
E n t F r
Z n # X X
Y / N
Y / N