L
NAPCO Security Systems
X
GEM-P1632 Programming Instructions
!
Page 27
SYSTEM OPTIONS (ADDRESS 0718-0722)
!
1. Select the desired option by circling
"
the data values for each digit (left and right).
!
2. Add the data values (ex: F=15=(1+2+4+8) from the selected options. See page 23).
!
3. Enter in address location (left and right digits).
NOTE:
Dark shaded data value box shows option not available.
!
4. Press
U
or
D
to save.
NOTE:
To select “Line-Fault Test only when Armed”, you must also select “Enable Line-Fault Test” at address 0721.
* NOTE:
If “Enable Global Ambush
Code” in Address 0720 is selected,
then program the 2-digit “Global
Ambush Code” in Address 1054. If
Address 1054 is left blank (•), then,
the 2-digit “Global Ambush Code”
will be “99”.
S
ys
tem
Op
tio
n
s
* NOTE:
Not for UL Installations.
[Default = blank (•) blank (•)]
§
This feature must be programmed in Fire
Alarm applications.
[Default = blank (•) blank (•)]
[Default = blank (•) blank (•)]
LEFT DIGIT (SUM
OF DATA VALUES)
RIGHT DIGIT (SUM
OF DATA VALUES)
ADDRESS 0718
LEFT DIGIT (SUM
OF DATA VALUES)
RIGHT DIGIT (SUM
OF DATA VALUES)
ADDRESS 0719
LEFT DIGIT (SUM
OF DATA VALUES)
RIGHT DIGIT (SUM
OF DATA VALUES)
ADDRESS 0720
[Default = blank (•) blank (•)]
LEFT DIGIT (SUM
OF DATA VALUES)
RIGHT DIGIT (SUM
OF DATA VALUES)
ADDRESS 0722
[Default = blank (•) blank (•)]
LEFT DIGIT (SUM
OF DATA VALUES)
RIGHT DIGIT (SUM
OF DATA VALUES)
ADDRESS 0721
RIGHT DATA
VALUES
(CIRCLE
"
)
SYSTEM OPTIONS
1
Interior Normally
Bypassed
2
Enable Global
Ambush Code *
4
Reset Day Zone with
Arm/Disarm Only
8
Enable
Residential Fire
RIGHT DATA
VALUES
(CIRCLE
"
)
SYSTEM OPTIONS
1
Auto Bell Test
on Arming
2
Auto Reset after Burglary
Output Timeout
4
Suppress Bypass
Reminder when Armed
8
Enable Local Alarm on
First Zone AND Trip
RIGHT DATA
VALUES
(CIRCLE
"
)
SYSTEM OPTIONS
1
Opening Report Only
after Alarm Report
2
Closing Report Only on
Conditional Close
4
Incl. Sel./Grp. Bypass in
Cond. Close /Status
8
Status
Report
RIGHT DATA
VALUES
(CIRCLE
"
)
SYSTEM OPTIONS
1
Enable Zone Doubling
(Zones 9-16)
2
Wireless Trouble
Activates Telco 1
4
Wireless Trouble
Activates Telco 3
8
Enable Alarm Output on Telco
Fail only when Armed
RIGHT DATA
VALUES
(CIRCLE
"
)
SYSTEM OPTIONS
1
Automatic Interior
Bypass/Easy Exit
2
Veri-phone Zones Trip
PGM2 Output
4
Veri-phone Audio Priority
Over Alarms
8
Resound on Wireless
Smoke Low Battery
SYSTEM OPTIONS
LEFT DATA
VALUES
(CIRCLE
"
)
Disable Keypad Function
Mode Download
1
Disable
Callback Download
2
Chirp Output on Keyfob
Arm/Disarm
4
Change Pulse Output to
Temporal Output
§
8
SYSTEM OPTIONS
LEFT DATA
VALUES
(CIRCLE
"
)
Access Control
on PGM2 Output
1
Maintained Keyswitch
Arming
2
Enable
Manager's Mode
4
Disable Keypad
Instant Mode
8
SYSTEM OPTIONS
LEFT DATA
VALUES
(CIRCLE
"
)
RESERVED
1
Enable AutoArm if not
closed at end of windows
2
Enable Time/Date
at Keypad
4
Disable Zone Fault
Scrolling
8
SYSTEM OPTIONS
LEFT DATA
VALUES
(CIRCLE
"
)
Don't Clear PGM2 Output
with Disarm
1
Disable 2nd Call Ans.
Machine Override
2
RESERVED
4
RESERVED
8
SYSTEM OPTIONS
LEFT DATA
VALUES
(CIRCLE
"
)
Line-Fault Test only
when Armed
1
Enable
Line-Fault Test
2
Inhibit System Trouble
Audible at Keypad
4
Select Alarm Output for
Keyfob Chirp
8
Default depends on Easy Menu Question
“
EZ ZONE DOUBLING? Y/N
”.
If yes, then [Default = •(blank) 1].
If no, then [Default = •(blank) •(blank)].