background image

L

 NAPCO Security Systems  

X

  GEM-P1632 Programming Instructions 

!

 

Page 27

 

SYSTEM OPTIONS (ADDRESS 0718-0722) 

!

1. Select the desired option by circling 

"

the data values for each digit (left and right).  

!

2. Add the data values (ex: F=15=(1+2+4+8) from the selected options.  See page 23). 

!

3. Enter in address location (left and right digits). 

 

NOTE:

  Dark shaded data value box shows option not available. 

!

4. Press 

U

 or 

D

 to save. 

NOTE:

 To select “Line-Fault Test only when Armed”, you must also select “Enable Line-Fault Test” at address 0721. 

* NOTE: 

If  “Enable Global Ambush 

Code” in Address 0720 is selected, 
then program the 2-digit “Global 
Ambush Code” in Address 1054. If 
Address 1054 is left blank (•), then, 
the 2-digit “Global Ambush Code” 
will be “99”. 

S

ys

tem
 Op
tio
n

s

 

* NOTE:  

Not for UL Installations. 

        [Default = blank (•) blank (•)] 

§

This feature must be programmed in Fire 

Alarm applications.

 

        [Default = blank (•) blank (•)] 

        [Default = blank (•) blank (•)] 

LEFT DIGIT (SUM 

OF DATA VALUES) 

RIGHT DIGIT (SUM 

OF DATA VALUES) 

 

 

ADDRESS 0718  

LEFT DIGIT (SUM 

OF DATA VALUES) 

RIGHT DIGIT (SUM 

OF DATA VALUES) 

 

 

ADDRESS 0719  

LEFT DIGIT (SUM 

OF DATA VALUES) 

RIGHT DIGIT (SUM 

OF DATA VALUES) 

 

 

ADDRESS 0720  

        [Default = blank (•) blank (•)] 

LEFT DIGIT (SUM 

OF DATA VALUES) 

RIGHT DIGIT (SUM 

OF DATA VALUES) 

 

 

ADDRESS 0722  

        [Default = blank (•) blank (•)] 

LEFT DIGIT (SUM 

OF DATA VALUES) 

RIGHT DIGIT (SUM 

OF DATA VALUES) 

 

 

ADDRESS 0721  

RIGHT DATA 

VALUES 

(CIRCLE 

"

)

 

SYSTEM OPTIONS 

Interior Normally 

Bypassed 

Enable Global 

Ambush Code * 

Reset Day Zone with 

Arm/Disarm Only 

Enable 

Residential Fire 

RIGHT DATA 

VALUES 

(CIRCLE 

"

)

 

SYSTEM OPTIONS 

Auto Bell Test 

on Arming 

Auto Reset after Burglary 

Output Timeout 

Suppress Bypass 

Reminder when Armed 

Enable Local Alarm on 

First Zone AND Trip 

RIGHT DATA 

VALUES 

(CIRCLE 

"

)

 

SYSTEM OPTIONS 

Opening Report Only 

after Alarm Report 

Closing Report Only on 

Conditional Close 

Incl. Sel./Grp. Bypass in 

Cond. Close /Status 

Status 

Report 

RIGHT DATA 

VALUES 

(CIRCLE 

"

)

 

SYSTEM OPTIONS 

Enable Zone Doubling  

(Zones 9-16) 

Wireless Trouble 

Activates Telco 1 

Wireless Trouble 

Activates Telco 3 

Enable Alarm Output on Telco 

Fail only when Armed 

RIGHT DATA 

VALUES 

(CIRCLE 

"

)

 

SYSTEM OPTIONS 

Automatic Interior  

Bypass/Easy Exit 

Veri-phone Zones Trip 

PGM2 Output 

Veri-phone Audio Priority 

Over Alarms 

Resound on Wireless 

Smoke Low Battery 

SYSTEM OPTIONS 

LEFT DATA 

VALUES 

(CIRCLE 

"

)

 

Disable Keypad Function 

Mode Download 

Disable 

Callback Download 

Chirp Output on Keyfob 

Arm/Disarm 

Change Pulse Output to 

Temporal Output

§

 

SYSTEM OPTIONS 

LEFT DATA 

VALUES 

(CIRCLE 

"

)

 

Access Control 

on PGM2 Output 

Maintained Keyswitch 

Arming 

Enable 

Manager's Mode 

Disable Keypad 

Instant Mode 

SYSTEM OPTIONS 

LEFT DATA 

VALUES 

(CIRCLE 

"

)

 

RESERVED 

Enable AutoArm if not 

closed at end of windows 

Enable Time/Date 

at Keypad 

Disable Zone Fault 

Scrolling 

SYSTEM OPTIONS 

LEFT DATA 

VALUES 

(CIRCLE 

"

)

 

Don't Clear PGM2 Output 

with Disarm 

Disable 2nd Call Ans. 

Machine Override

 

RESERVED 

RESERVED 

SYSTEM OPTIONS 

LEFT DATA 

VALUES 

(CIRCLE 

"

)

 

Line-Fault Test only  

when Armed 

Enable 

Line-Fault Test 

Inhibit System Trouble 

Audible at Keypad 

Select Alarm Output for 

Keyfob Chirp 

Default depends on Easy Menu Question  

EZ ZONE DOUBLING? Y/N

”.  

If yes, then [Default = •(blank) 1].  
If no, then [Default = •(blank) •(blank)]. 

Summary of Contents for Gemini GEM-P1632

Page 1: ...p 5 Dealer Code Quick Start for GEM K3DGTL 1 Refer to the wiring diagram connect Siren Aux Power PGM Output Remote Bus Earth Ground Zone and Tele phone Wiring NOTE See Installation Instructions WI808...

Page 2: ...27 All references to 0720 Bit 6 Enable PGM2 Chirp on Keyfob Arming name changed to Chirp Output on Keyfob Arm Disarm Page 27 All references to 0722 Bit 0 Automatic Interior Bypass name changed to Aut...

Page 3: ...tral Station Receiver 1 Account Number 16 Central Station Receiver 1 Format 16 Enter User Codes 16 RF Transmitter Points 17 Key Fob Transmitters 18 Key Fob Transmitters as Zone Input Devices 18 Dealer...

Page 4: ...amming The Direct Address Program Mode is an extension of the Dealer Program Mode wherein data is entered at the keypad by specific location This mode is accessed from the Easy Menu Driven Program Mod...

Page 5: ...Dealer Program Mode when finished Dealer Code Default 456789 Number of Zones in Area 1 Panel Zone Doubling Fire Zones in Area 1 2 Wire Fire Zones in Area 1 Local or Central Station Reporting System Ex...

Page 6: ...ton Fire Zones in Area 1 Appears for New Panel Only Enter the zone number of any zones which are to be used as Fire Zones both 2 wire 4 wire or wireless Valid entries are from 01 to 32 Directly enter...

Page 7: ...e a distinct pulsating tone when zone is faulted Exit Entry2 Zones in Area 1 New Program Only Enter the zone numbers of zones to be used as Exit Entry zones Valid entries are from 01 to 32 Directly en...

Page 8: ...NEXT YES button to enable Press the PRIOR NO button to continue The SIA CP 01 Features are designed to reduce the incidence of false alarms See WI808 Installer Program ming Quick Reference Chart SIA...

Page 9: ...s with Area 1 and Area 2 Options Press R once to set the cursor to the User Code Use the number buttons 1 through 9 to enter a code from 3 to 6 digits Enter up to 6 digits 4 digits is recommended in t...

Page 10: ...sarm this area Arm Only Prevents User Code from disarming this area Service A Service Code has restricted arm disarm rights if an area is armed with a Service Code a MONITOR ON appears on the GEM RP2A...

Page 11: ...panic buttons on a system each reporting to a Central Station or a pager and or annunciating on a keypad the key fob zone number with description location To assign a key fob to a zone program the key...

Page 12: ...U button Data entry is not allowed NOTE Enter Easy Menu Driven Program Mode to program system again Cold Start Erases Entire Program This erases the entire program including Dealer Program by erasing...

Page 13: ...tions Fire Zones Appears for New Panel Only Enter the zone number of any Fire Zones both 2 wire 4 wire or wireless Valid entries are from 01 to 32 Directly enter each zone number including leading zer...

Page 14: ...rogram Only Enter the zone numbers of zones to be used as Exit Entry zones Valid entries are from 01 to 32 Directly enter each zone number including leading zeros Press U to save and repeat for any ad...

Page 15: ...YES button to program all zones except 24 Hr fire zones for No End Of Line Resistor Press the PRIOR NO button to continue Do not program this feature for UL Installations Enable Telco Line Fault Test...

Page 16: ...s for each code Refer to the tables below for available data entries for User Options Press R once to set cursor to the User Number and enter the desired User Number Press R once again to set the curs...

Page 17: ...h 27 displayed in keypad window press R 0 2 User 2 R 1234 G 0 G 0 User Code 09 User Area 1 options 00 User Area 2 Options and U save Notes 1 For User Code press G 0 for Blank Space 2 For User Options...

Page 18: ...ng leading zeros Use the 1 through 9 buttons NOTE Press 0 for a zero Press U to save Re enter the Dealer Code to verify the previous code Press U to save Press the NEXT YES but ton to proceed NOTE The...

Page 19: ...L NAPCO Security Systems X GEM P1632 Programming Instructions Page 19 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 20: ...nge all the options It consists of multiple address locations with two data entry locations each left and right as shown in the adjacent diagram ACCESSING DIRECT ADDRESS PROGRAM MODE LEFT DIGIT RIGHT...

Page 21: ...M K3DGTL Keypads To access press C in Dealer Program Mode 1 Toggle Cursor to 4 digit ad dress field using the R button 2 Enter address Number directly using number buttons 0 9 3 Enter Data directly us...

Page 22: ...KEYPAD DISPLAYS 8 4 2 1 blank 0 8 4 2 1 1 1 8 4 1 2 2 2 8 4 3 3 3 8 2 1 4 4 4 8 2 5 5 5 8 1 6 6 6 8 7 7 7 4 2 1 8 8 8 4 2 9 9 9 4 1 10 G 0 0 4 11 G 1 B 2 1 12 G 2 C 2 13 G 3 D 1 14 G 4 E 15 G 5 F DATA...

Page 23: ...ch address CONVENTIONS USED IN THIS MANUAL The Keypad Programming Worksheets in the back are provided as an address programming reference to help the installer modify his custom default program or to...

Page 24: ...try in the boxes shown 4 For more information on a programming option refer to the Glossary at the end of this manual EXIT ADDRESS 0000 DELAY LEFT RIGHT sec Default 3 C ENTRY ADDRESS 0001 DELAY 1 LEFT...

Page 25: ...save PAGER FORMAT OPTIONS ADDRESS 0256 0257 LEADING DIGITS FOR PAGER FORMAT In Pager Format reporting the message typically begins with 00 However for some pager services this will cause the Pager s...

Page 26: ...Output 8 4 2 1 0463 8 4 2 1 Report Event Telco 1 8 4 2 1 0464 8 4 2 1 Report Restore Telco 1 8 4 2 1 0465 8 4 2 1 Report Event Telco 3 8 4 2 1 0468 8 4 2 1 Report Restore Telco 3 8 4 2 1 0469 8 4 2 1...

Page 27: ...PTIONS 1 Auto Bell Test on Arming 2 Auto Reset after Burglary Output Timeout 4 Suppress Bypass Reminder when Armed 8 Enable Local Alarm on First Zone AND Trip RIGHT DATA VALUES CIRCLE SYSTEM OPTIONS 1...

Page 28: ...S CIRCLE SYSTEM OPTIONS 1 Enable Keypad Set Time Date Message 2 Enable Cancel Report to Telco 3 4 Disable ON OFF as Easy Exit 8 Enable GEM PRINT Module Lug E15 Output Mode ADDRESS 1061 LEFT RIGHT blan...

Page 29: ...E Leave trailing boxes blank For a zero press G0 3 Valid entries are 1 9 B button C button D 3 sec pause E Wait for dial tone F ignore location Press U or D to save Default for CS R e c e i v e r 1 Te...

Page 30: ...TS 1 4 CS Telco 3 Subscriber 0303 0304 0305 0306 Opening Closing ID R R R R Number Area 2 ADDRESS 0303 0306 RIGHT DIGITS 1 4 CS Telco 1 Subscriber 0267 0268 0269 0270 Event ID R R R R Number Area 1 AD...

Page 31: ...t digit is 3 then the reporting code is 39 For example for zone 15 address 0372 if the right digit is 4 then the reporting code is 45 MODEM CODES determine the zone types reported for the following fo...

Page 32: ...r 11 User 10 User 9 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUES ADDRESS 0448 User Closing Telco 1 User 32 User 31 User 30 User 29 LEFT RIGHT User 28 User 27 User 26 User 25 8 4 2 1 8 4 2 1 RIGH...

Page 33: ...aded data value box shows option not available 3 Press U or D to save AREA ARMING OPTIONS ADDRESS 0743 0744 PRIORITY AREA ARMING 1 Select option from the table shown 2 Enter in corresponding right dig...

Page 34: ...NOTE Dark shaded data value box shows option not available 4 Press U or D to save Area Bell Control Options RIGHT DATA VALUES CIRCLE Disarming Area 1 1 Area 1 Burg Output Silenced 2 Area 2 Burg Outpu...

Page 35: ...in corresponding right and left digit address locations above 3 Press U or D to save KEYPAD OPTIONS ADDRESS 0723 0736 RIGHT OPTION blank Disabled 1 Active Keypad KEYPAD ASSIGNMENT KEYPAD NO KEYPAD OPT...

Page 36: ...ower 8 4 2 1 0561 8 4 2 1 8 4 2 1 0506 8 4 2 1 Auto Reset 8 4 2 1 0562 8 4 2 1 8 4 2 1 0507 8 4 2 1 Swinger Shutdown 8 4 2 1 0563 8 4 2 1 8 4 2 1 0508 8 4 2 1 Chime 8 4 2 1 0564 8 4 2 1 8 4 2 1 0509 8...

Page 37: ...2 1 8 4 2 1 0612 8 4 2 1 PGM2 Output 8 4 2 1 0668 8 4 2 1 8 4 2 1 0613 8 4 2 1 Entry Exit 1 8 4 2 1 0669 8 4 2 1 8 4 2 1 0614 8 4 2 1 Entry Exit 2 8 4 2 1 0670 8 4 2 1 8 4 2 1 0615 8 4 2 1 Exit Entry...

Page 38: ...811 0812 0813 L R L R L R L R L R 0814 RELAY AREA Timeout Event ID COND ADDRESS 0815 0819 RELAY EVENT 14 0815 0816 0817 0818 L R L R L R L R L R 0819 RELAY AREA Timeout Event ID COND ADDRESS 0820 0824...

Page 39: ...D 8 Area 1 General System Alarm D 9 Area 2 General System Alarm F blank Relay Control Group 1 F 1 Relay Control Group 2 F 8 Entry Relay Area 1 F 9 Entry Relay Area 2 LEFT DATA ENTRIES ALARM TYPE TIMEO...

Page 40: ...locations above right digit only left digit is not used 3 Press U or D to save NOTE These timers apply only to Supervised RF Transmitters see RF Transmitters in Easy Menu Driven Mode Programming Defa...

Page 41: ...sed for programming however this keypad may be located in any area The Program Mode cannot be accessed while the communicator is transmitting except during the first three minutes after power up After...

Page 42: ...s directly using number buttons 0 9 4 Press the U button to save each code NOTE Press G 0 button to clear character at cursor To continue press P or Q button G E M I N I ARMED COMPUTERIZED SECURITY SY...

Page 43: ...panel Keypads 1 7 Each must be configured for a keypad address In addition the keypad may be configured to disable a touchpad backlight b LCD backlight and c entry sounder Keypads are configured by t...

Page 44: ...dress 0720 27 Clear Dealer Program Direct Address 1197 41 Closing Report Only on Conditional Close Direct Address 0718 27 Cold Start Direct Address 1198 41 CS AREA SYSTEM REPORTING OPTIONS Direct Addr...

Page 45: ...or Stay Bypass Enable Zone Direct Address 0528 0583 0638 0693 36 37 Interior Normally Bypassed Direct Address 0720 27 Key fob Transmitters Easy Menu Driven N A 11 18 KEYPAD OPTIONS Direct Addresses 07...

Page 46: ...sses 0478 0485 26 SYSTEM RESPONSE ACTIVATED BY GLOBAL EVENT TROUBLE Direct Addresses 0460 0469 26 Test Timer Direct Address 0332 30 Touch tone Dialing w Rotary Backup Direct Address 0394 31 Trouble on...

Page 47: ...0 0319 0350 CENTRAL STATION SYSTEM REPORTING CODES Direct Addresses 30 0330 Cancel Report Code Direct Address 30 0332 Test Timer Direct Address 30 0358 0389 CS ZONE REPORTING OPTIONS Direct Addresses...

Page 48: ...t Address 36 37 0538 Sensor Watch Enable Zone Direct Address 36 37 0540 Chime 2 Enable Zone Direct Address 36 37 0546 Priority Enable Zone Direct Address 36 37 0547 Priority with Bypass Enable Zone Di...

Page 49: ...ct Address 36 37 0617 Auto Reset Enable Zone Direct Address 36 37 0618 Swinger Shutdown Enable Zone Direct Address 36 37 0619 Chime Enable Zone Direct Address 36 37 0620 Abort Delay Enable Zone Direct...

Page 50: ...Address 36 37 0690 Trouble on Short Enable Zone Direct Address 36 37 0691 Zone Area 1 Enable Zone Direct Address 36 37 0692 Zone Area 2 Enable Zone Direct Address 36 37 0693 Interior Stay Bypass Enab...

Page 51: ...e Low Battery Direct Address 27 0722 Veri phone Priority Zones over Alarms Direct Address 27 0722 Veri phone Audio Priority Over Alarms Direct Address 27 0722 Veriphone Zones trip PGM2 Output Direct A...

Page 52: ...REFER TO WI808 FOR COMPATIBLE TWO WIRE SMOKE DETECTORS DO NOT MIX DIFFERENT MODELS 7 RECOMMENDED BATTERIES YUASA NP4 12 OR NP7 12 BATTERY SHOULD BE REPLACED EVERY 5 YEARS 8 THIS PANEL SHALL BE CHECKED...

Reviews: