Software Release: [TBD]
Section 40
28
00-02-1167
2018-09-18
No Speed During Crank:
If during the first crank, the controller does not see a speed signal from the
designated speed source before this delay expires, the controller will shutdown on “No Speed Signal”.
Factory set to 00:00:06.
Warnings and Shutdowns
(Low Security)
:
establish alerts for the listed parameters. When values reach
the set points in this menu the controller will show
INTERNAL FAULT
on the top left of the screen. If
nuisance faults keep occurring lower or raise the set point within this menu.
Low Oil Pressure Shutdown
(High Security)
:
a shutdown will occur when the pressure reaches
this set point.
Factory set to 10 PSI.
Low Oil Pressure Warning
(High Security)
:
an alarm will occur when the pressure reaches this
set point.
Factory set to 15 PSI.
High Engine Temp Shutdown
(Medium Security)
:
a shutdown will occur when the temperature
reaches this set point.
Factory set to 225 F.
High Engine Temp Warning
(Medium Security)
:
an alarm will occur when the temperature
reaches this set point.
Factory set to 210 F.
High Oil Temp Shutdown
(Medium Security)
:
a shutdown will occur when the temperature
reaches this set point.
Factory set to 225 F.
High Oil Temp Warning
(Medium Security)
:
an alarm will occur when the temperature reaches
this set point.
Factory set to 210 F.
Low Fuel Level Shutdown
(Medium Security)
:
a shutdown will occur when the level reaches this
set point.
Factory set to 5%.
Low Fuel Level Warning
(Medium Security)
:
an alarm will occur when the level reaches this set
point.
Factory set to 10%.
High Battery Warning
(Low Security)
:
an alarm will occur when the VDC reaches this set point.
Factory set to 16.0 VDC.
Low Battery Warning
(Low Security)
:
an alarm will occur when the VDC reaches this set point.
This setting is armed after crank disconnect upon startup.
Factory set to 8.0 VDC.
Weak Battery Warning
(Low Security)
:
an alarm will occur when the VDC reaches this set point.
Factory set to 6.0 VDC.
Underspeed Shutdown
(Medium Security)
:
a shutdown will occur when the engine speed
reaches this set point.
Factory set to 0 RPM
Overspeed Shutdown
(Medium Security)
:
a shutdown will occur when the engine speed reaches
this set point.
Factory set to 2400 RPM.
Test Run
(High Security)
:
This allows running the generator with the frequency alarms disabled.
Disable/Enabled.
Factory set to Disabled