Software Release: [TBD]
Section 40
29
00-02-1167
2018-09-18
Input / Output Menu
Digital Inputs (1-5)
(Medium Security)
:
for each of the digital inputs, the ability to select the following
parameters exists:
Digital input 1
(Medium Security)
: Factory set to Function: Stop Button, Active: B-, Action: Not
Used
Digital Input 2
(Medium Security)
: Factory set to Function: Transfer Switch, Active: B-, Action:
Not Used
Digital Input 3 (Medium Security)
: Factory set to Function: Disabled, Active: B-, Action: Not
Used
Digital Input 4 (Medium Security)
: Factory set to Function: Disabled, Active: B-, Action:
Shutdown
Digital Input 5
(Medium Security)
: Factory set to Function: Disabled, Active: B-, Action:
Shutdown
Function (Medium Security)
:
Disabled
Transfer Switch
Remote Alarm Acknowledge
Low Fuel Level
Fuel Leak
Fuel Filter Restriction
Low Lube Oil Level
Low Coolant Level
Stop Button
Remote Manual/Auto
Water in Fuel
No Flow
User 1
User 2
Air Damper Closed
Air Filter Restriction
Battery Charger Fail
Oil Filter Restriction
Low Oil Pressure
High Engine Temperature
Active (Medium Security)
:
B-
(when input closes to ground it enables action of digital function)
B+
(when input closes to battery positive it enables action of digital function)
Open
(when input opens it enables action of digital function)
Action (Medium Security)
:
Not Used:
(chosen when using digital input for anything except a fault)
Warning:
(chosen for an immediate warning to the operator when function is active)
Shutdown:
(chosen for an immediate shutdown of engine when function is active)
Shutdown, Controlled:
(chosen to allow the controller to shutdown through the normal
sequence of operation including cooldown when function is active. User acknowledgement of
the fault is required to restart in Auto after shutdown occurs)
Relay Control:
(chosen for control of one of the relay outputs when function is active)
Shutdown, Controlled, Restart:
(chosen to allow the controller to shutdown through the
normal sequence of operation including cooldown when function is active. User
acknowledgement of the fault is
NOT
required to restart in Auto after shutdown occurs if
active shutdown is removed from controller)