Cooldown Delay
(Low Security)
:
allows the operator to set the desired cool-down time/delay for the
engine. This is the length of time the engine will run at a lower speed for its cool-down cycle.
Factory set
to 3 minutes
Advanced Engine Settings
(Low Security)
Address Claim
(High Security)
:
allows the operator to set the address claim of the controller when used
on the CANbus. This address is relative to the address the ECU requires the TSC1 to be broadcast from
along with any Tier 4 messaging. Consult your engine manufacturer or dealer to obtain the correct source
address the controller should be set to communicate correctly with the engine ECU.
Factory set to 3
and
changed per Engine Manufacturer setting
ECU Source Address
(High Security)
:
source address of the ECU being connected to. Normally set to
0, 1 or 2
per SAE J1939 specifications. This menu item is only shown if J1939 is selected for the Engine
Type.
Factory set to 0
ECU Hour Select
(High Security)
:
choose from ECU Hours (engine hours reported by the ECU) or Internal
(hours calculated internally by the MGC1000) provided the RPM>50. This menu item is only shown if J1939
is selected for the Engine Type.
Factory set to ECU Hours
Crank Attempts
(High Security)
:
format of 1.00 to 20.00. The number of times the engine will attempt to
start before providing an overcrank shutdown.
Factory set to 3
Crank Disconnect Speed
(Medium Security)
:
the speed at which the crank will disconnect barring other
input parameters.
Factory set to 500 RPM
Run To Destruct
(High Security)
:
this feature is used when the controller is not able to shut down the
engine, but allows faults to be shown on screen and LEDs per application requirement.
Factory set to
Disable
Timers/Delays
(Low Security)
:
establish operational settings for:
Auto Start Delay
(Medium Security)
:
the auto start condition must remain active throughout this
delay for an auto start to occur. If the auto start condition is removed during this delay, the delay
is reset to zero.
Factory set to 3 seconds
Auto Stop Delay
(Medium Security)
:
this auto stop condition must remain active throughout this
delay for an auto stop to occur. If the auto stop condition is removed during this delay, the delay is
reset to zero.
Factory set to 3 seconds
ECU Stabilize Timer
(High Security)
:
on start-ups, this delay allows the ECU to stabilize and
broadcast on the CAN bus prior to actual cranking.
Factory set to 5 seconds
Crank Time
(High Security)
:
this is the length of time the crank output is turned on during cycle
cranking.
Factory set to 10 seconds
Crank Rest
(High Security)
:
this is the length of time the crank output is turned off during cycle
cranking.
Factory set to 10 seconds
Prestart Delay 1
(Low Security)
:
after a start condition has been accepted by the controller, this
delay begins timing, and the prestart #1 output turns on. When this delay expires, the output is
turned off, and the auto sequence continues.
Auto Only
(Medium Security)
: Factory set to Disabled.