Analog Inputs (1-3)
(Medium Security)
:
for each of the analog inputs, the ability to select the following
parameters exists:
Analog input 1 (Medium Security)
: Factory set to Function: Disabled
Analog Input 2 (Medium Security)
: Factory set to Function: Disabled
Analog Input 3 (Medium Security)
: Factory set to Function: Disabled
Function (Medium Security)
:
Disabled
Datcon Oil Pressure
Murphy Oil Pressure
(ES2P-100)
VDO5 Bar Oil Pressure
VDO7 Bar Oil Pressure
Murphy Engine Temp
(ES2T-250/300)
Datcon Engine Temp
VDO Engine Temp
Murphy Fuel Level
(ES2F)
VDO Fuel Level
Datcon Fuel Level
Murphy Oil Temp
(ES2T-250/300)
Datcon Oil Temp
VDO Oil Temp
Murphy PMK-400 Pressure
(Gear Box Pressure, Murphy PMK-400 Sensor)
Analog.Digital1
Relay (1-3) and Digital (1-4) Outputs
(Medium Security)
:
these same parameters are used for both the
Relay and Digital Outputs.
Relay 1
(Medium Security)
:
Factory set to Crank, Starter Relay
Relay 2
(Medium Security)
:
Factory set to ECU Enable
Relay 3
(Medium Security)
:
Factory set to Not Used
DO1
(B+, 1A) (Medium Security)
:
Factory set to Prestart 1 Delay
DO2
(B+, 1A) (Medium Security)
:
Factory set to AC Contactor
DO3
(B-, 1A) (Medium Security)
:
Factory set to Not Used
DO4
(B-, 1A) (Medium Security)
:
Factory set to Not Used
Not Used:
This function does not allow the output to turn on when chosen.
Prestart 1 Delay:
Output turns on when in Prestart 1 state. See Timers on page 23.
Prestart 2 Delay:
Output turns on when in Prestart 2 state. See Timers on page 23.
Crank:
Output turns on when in Crank state. See Timers on page 23.
Fuel:
Output turns on when cranking and turns off after cooldown. See Timers on page
23.
ECU Enable
Used for enabling the ECU on electronic engines. This output turns on
anytime the controller is powered up or in the crank/run state. It’s turned off if the controller
is in spindown or standby states.
Excite Engine Alternator
This output can be used if the dedicated Alt Excite output is not
used.
Shutdown
This output turns on when a fault shutdown occurs.
Common Alarm
This output turns on when either a shut-down or a non-shutdown warning
occurs.
Remote Alarm
This output turns on when a either a shutdown or a non-shutdown warning
occurs.
Not in Auto
This output turns on when the controller is in the manual mode.