Software Release: [TBD]
Section 40
14
00-02-1167
2018-09-18
3. Access
Analog Inputs
and assign one Analog input for Oil Pressure and one for Engine Temperature.
Press
[Enter]
to save the settings.
4. Press
[Back]
and access Relay and Digital Outputs.
5. Press down arrow to
Relay1-3 or DO1-4
, and assign desired outputs for Crank, Fuel, Prestart, etc.
6. Press the
[Back]
key and up arrow to
Advanced Engine Settings
, and press
[Enter].
7. Press down arrow to
Warnings and Shutdowns
, press
[Enter]
.
8. Ensure all warnings and shutdowns are set to the appropriate settings for the engine for engine faults
such as oil pressure and coolant temperature.
9. Press the
[Back]
key twice and up arrow to
System
, and press
[Enter].
10. Press down arrow to
Set Machine Hours,
select desired machine/internal hours then press
[Enter]
.
11. Press the
[Menu]
key to exit the menu setup screens.
J1939 Electronic Engine Setup (Factory Default)
1. Access
Menu/Engine Settings/Engine Type
to ensure J1939 is selected.
2. Press down arrow to
Engine Manufacturer
, select which engine manufacturer the controller is/will be
used then press
[Enter]
.
3. Press down arrow to
Engine Emission
, select the emissions level of the engine then press
[Enter]
.
4. Press down arrow to
Tier 4
(if a Tier 4 selection is made in Engine Emission menu), press
[Enter].
a. Press down arrow to
DEF Gauge
. Select Yes to show this gauge (if needed) then press
[Enter]
.
b. Press down arrow to
Percent Soot Gauge
. Select Yes to show this gauge (if needed) then
press
[Enter]
.
c. Press down arrow to
Regen Screen
. Select Yes to show this screen (if desired) then press
[Enter]
.
5. Press the
[Back]
key and down arrow to
Advanced Engine Settings
, and press
[Enter]
.
6. Ensure
Address Claim
is set to the CAN address from which the Tier 4 regeneration is expected to
be sent to the engine ECU (this is often times designated by the manufacturer/distributor).
7. Press down arrow to
Warnings and Shutdowns
, press
[Enter]
.
8. Ensure all warnings and shutdowns are below or above ECU settings if required to have the ECU
shutdown the engine instead of the MGC1000 (for engine faults such as oil pressure and coolant
temperature).
NOTE:
If requiring the engine ECU to shutdown the engine on any engine shutdown
fault without help from the controller, select ECU Shutdowns in the System Menu and
change the setting to ECU Only.
9. Press the
[Back]
key and down arrow to
Input/Output
, and press
[Enter]
.
10. Press down arrow to access
Analog Inputs,
ensure the analog inputs aren't set to oil pressure or
coolant temp (disable or change to something different).
11. Press down arrow to
Relay1-3 or DO1-4
, and assign desired outputs for Crank, ECU Enable, Prestart,
etc.
12. Press the
[Menu]
key to exit the menu setup screens.
Summary of Contents for PowerCore MGC1000
Page 4: ...Software Release TBD Section 40 4 00 02 1167 2018 09 18 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 46: ...Software Release TBD Section 40 46 00 02 1167 2018 09 18 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 47: ...Software Release TBD Section 40 47 00 02 1167 2018 09 18 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 48: ......