Troubleshooting
Electrical Control System
137
2.4.4.16. J0 malfunction
P7 display
P7 display
High temperature protection of
evaporator
High temperature protection of
evaporator
Whether compressor
operates?
Whether compressor
operates?
Yes
Check whether the outdoor
ambient temperature is higher
than 30
℃
Check whether the outdoor
ambient temperature is higher
than 30
℃
No
Correct the connection
Correct the connection
No
Check the connection
between T2 and PCB.
Check whether T2 and T2B
Is reversed
Check the connection
between T2 and PCB.
Check whether T2 and T2B
Is reversed
Check whether the
resistance of T2 is normal
refer to the
Appendix
1
Check whether the
resistance of T2 is normal
refer to the
Appendix
1
Replace the temperature sensor
Replace the temperature sensor
No
Yes
Yes
Stop the unit
Stop the unit
Yes
Check whether the air-outlet is
blocked?
Check whether the air-outlet is
blocked?
Check whether the heat
exchanger and filter are
dirty
?
Check whether the heat
exchanger and filter are
dirty
?
Check whether the indoor fan
is running normal?
Check whether the indoor fan
is running normal?
No
Yes
Clean the air-outlet
Clean the air-outlet
Replace the indoor main
PCB
Replace the indoor main
PCB
Clean the heat exchanger and filter
Clean the heat exchanger and filter
Yes
No
Yes
please refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
please refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
No
No
J0
Summary of Contents for MUCR-H6 Series
Page 15: ...Air Velocity Distributions Reference Data Indoor Units 13 30 42K Cooling Heating ...
Page 16: ...Air Velocity Distributions Reference Data 14 Indoor Units 48 60K Cooling Heating ...
Page 21: ...Field Wiring Indoor Units 19 10 Field Wiring ...
Page 30: ...Static Pressure 28 Indoor Units 5 Static Pressure MUCR 12 H6 MUCR 18 H6 ...
Page 31: ...Static Pressure Indoor Units 29 MUCR 24 H6 MUCR 30 H6 ...
Page 32: ...Static Pressure 30 Indoor Units MUCR 36 H6 MUCR 42 H6 MUCR 48 H6 MUCR 48 H6T MUCR 60 H6T ...
Page 41: ...Service Space Indoor Units 39 3 Service Space ...
Page 52: ...50 Indoor Units 10 Field Wiring ...
Page 61: ...Field Wiring Indoor Units 59 10 Field Wiring MUCSR 12 H6 MUCSR 18 H6 ...
Page 64: ...Dimensions 62 Outdoor Units Model Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Page 95: ...Refrigerant pipe installation Installation 93 ...