Troubleshooting
134
Electrical Control System
2.4.4.13. J2 malfunction
When
compressor discharge temperature is higher than 115°C, the unit will stop, and unit runs again when
compressor discharge temperature is lower than 90°C.
P4 display
P4 display
Temperature protection of
compressor discharge
Temperature protection of
compressor discharge
Check whether the
compressor discharge temp. is
more than 115°C ?
Check whether the
compressor discharge temp. is
more than 115°C ?
Check
whether
the
connection is right between
compressor discharge temp.
sensor and PCB according
to wiring diagrams?
Check
whether
the
connection is right between
compressor discharge temp.
sensor and PCB according
to wiring diagrams?
Measure the resistance value
of compressor discharge
temp. sensor. If the value is
not normal
is normal refer to
the
Appendix
2?
Measure the resistance value
of compressor discharge
temp. sensor. If the value is
not normal
is normal refer to
the
Appendix
2?
No
Yes
Yes
No
Correct the wiring connection
Correct the wiring connection
Stop leaking and add refrigerant
Stop leaking and add refrigerant
Replace the compressor discharge temp. sensor
Replace the compressor discharge temp. sensor
No
Yes
Replace high pressure valve assy
Replace high pressure valve assy
Yes
No
Replace outdoor main PCB
Replace outdoor main PCB
No
Check whether the
refrigerant is leak
Check whether the
refrigerant is leak
J2
Summary of Contents for MUCR-H6 Series
Page 15: ...Air Velocity Distributions Reference Data Indoor Units 13 30 42K Cooling Heating ...
Page 16: ...Air Velocity Distributions Reference Data 14 Indoor Units 48 60K Cooling Heating ...
Page 21: ...Field Wiring Indoor Units 19 10 Field Wiring ...
Page 30: ...Static Pressure 28 Indoor Units 5 Static Pressure MUCR 12 H6 MUCR 18 H6 ...
Page 31: ...Static Pressure Indoor Units 29 MUCR 24 H6 MUCR 30 H6 ...
Page 32: ...Static Pressure 30 Indoor Units MUCR 36 H6 MUCR 42 H6 MUCR 48 H6 MUCR 48 H6T MUCR 60 H6T ...
Page 41: ...Service Space Indoor Units 39 3 Service Space ...
Page 52: ...50 Indoor Units 10 Field Wiring ...
Page 61: ...Field Wiring Indoor Units 59 10 Field Wiring MUCSR 12 H6 MUCSR 18 H6 ...
Page 64: ...Dimensions 62 Outdoor Units Model Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Page 95: ...Refrigerant pipe installation Installation 93 ...