Additional refrigerant charge
Installation
99
8. Additional refrigerant charge
After the vacuum drying process is carried out, the additional refrigerant charge process need to be
performed.
The outdoor unit is factory charged with refrigerant. The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe between indoor and outdoor unit. Refer the following
formula to calculate the charge volume.
Diameter of liquid pipe (mm)
Φ6.
35
Φ9.5
2
Formula
V=15g/m×(L-5)
V=30g/m×(L-5)
V: Additional refrigerant charge volume (g).
L :
The length of the liquid pipe (m).
Note:
Refrigerant may only be charged after performed the vacuum drying process.
Always use gloves and glasses to protect your hands and eyes during the charge work.
Use electronic scale or fluid infusion apparatus to weight refrigerant to be recharged. Be sure to avoid
extra refrigerant charged, it may cause liquid hammer of the compressor or protections.
Use supplementing flexible pipe to connect refrigerant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be charged in liquid state. Before recharging, The air in the flexible pipe and
manifold gauge should be exhausted.
After finished refrigerant recharge process, check whether there is refrigerant leakage at the connection
joint part.(Using gas leakage detector or soap water to detect).
Summary of Contents for MUCR-H6 Series
Page 15: ...Air Velocity Distributions Reference Data Indoor Units 13 30 42K Cooling Heating ...
Page 16: ...Air Velocity Distributions Reference Data 14 Indoor Units 48 60K Cooling Heating ...
Page 21: ...Field Wiring Indoor Units 19 10 Field Wiring ...
Page 30: ...Static Pressure 28 Indoor Units 5 Static Pressure MUCR 12 H6 MUCR 18 H6 ...
Page 31: ...Static Pressure Indoor Units 29 MUCR 24 H6 MUCR 30 H6 ...
Page 32: ...Static Pressure 30 Indoor Units MUCR 36 H6 MUCR 42 H6 MUCR 48 H6 MUCR 48 H6T MUCR 60 H6T ...
Page 41: ...Service Space Indoor Units 39 3 Service Space ...
Page 52: ...50 Indoor Units 10 Field Wiring ...
Page 61: ...Field Wiring Indoor Units 59 10 Field Wiring MUCSR 12 H6 MUCSR 18 H6 ...
Page 64: ...Dimensions 62 Outdoor Units Model Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Page 95: ...Refrigerant pipe installation Installation 93 ...