Electrical Control Function
108
Electrical Control System
1.3.3.2 Indoor fan running rules:
In heating mode, indoor fan can be selected as high, medium, low, auto and silent. The anti-cold- wind
function has the priority.
When the compressor is running, the indoor fan is controlled as below:
Setting fan
speed
Actual fan speed
H
(
=H
)
H+(H+=H+G)
M(M=M)
M+(M+=M+Z)
L(L=L)
L+(L+=L+D)
H-
(
H-=H-G)
M-(M-=M-Z)
L-(L-=L-D)
T1-Td
℃
L
H
M
-
If the compressor stops caused by the room temperature rising, the indoor fan will be forced to run 127
seconds with breeze. During this period, the anti-cold-wind is disabled.
Auto fan action in heating mode:
T1-Td
L
(H+-L)*0.4+L
(H+-L)*0.6+L
H+
(H+-L)*0.8+L
(H+-L)*0.6+L
(H+-L)*0.2+L
1.3.3.3 Defrosting mode
:
Condition of defrosting:
AC will enter the defrosting mode according to the value of temp. of T3 and the value range of temp. change
of T3 and also the compressor running time.
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will finish and the machine will turn to normal
heating mode.
----T3 rises to be higher than TCDE1
℃
.
----T3 keeps to be higher than TCDE2
℃
for 80 seconds.
----The machine has run for 10 minutes in defrosting mode.
Summary of Contents for MUCR-H6 Series
Page 15: ...Air Velocity Distributions Reference Data Indoor Units 13 30 42K Cooling Heating ...
Page 16: ...Air Velocity Distributions Reference Data 14 Indoor Units 48 60K Cooling Heating ...
Page 21: ...Field Wiring Indoor Units 19 10 Field Wiring ...
Page 30: ...Static Pressure 28 Indoor Units 5 Static Pressure MUCR 12 H6 MUCR 18 H6 ...
Page 31: ...Static Pressure Indoor Units 29 MUCR 24 H6 MUCR 30 H6 ...
Page 32: ...Static Pressure 30 Indoor Units MUCR 36 H6 MUCR 42 H6 MUCR 48 H6 MUCR 48 H6T MUCR 60 H6T ...
Page 41: ...Service Space Indoor Units 39 3 Service Space ...
Page 52: ...50 Indoor Units 10 Field Wiring ...
Page 61: ...Field Wiring Indoor Units 59 10 Field Wiring MUCSR 12 H6 MUCSR 18 H6 ...
Page 64: ...Dimensions 62 Outdoor Units Model Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Page 95: ...Refrigerant pipe installation Installation 93 ...