Troubleshooting
Electrical Control System
125
2.4.4.3 MCE malfunction
Yes
Replace the compressor driven chip,
Replace the compressor driven chip,
Power off, then restart the
unit 2 minutes later
Power off, then restart the
unit 2 minutes later
MCE malfunction
MCE malfunction
2.4.4.4. F4 malfunction
Yes
Replace the outdoor main PCB
Replace the outdoor main PCB
Power off, then restart the
unit 2 minutes later
Power off, then restart the
unit 2 minutes later
Outdoor EEPROM malfunction
Outdoor EEPROM malfunction
F4- Display
F4- Display
EEPROM: An electrically erasable programmable read-only memory whose contents can be erased and
reprogrammed using a pulsed voltage.