Troubleshooting
136
Electrical Control System
2.4.4.15. P0 malfunction
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or
close to 0, the IPM is defective. Otherwise, please follow the procedure below:
P6 display
P6 display
IPM module protection
IPM module protection
Yes
Check whether the power voltage
is normal.
Check whether the power voltage
is normal.
Measure whether outdoor terminal
voltage is normal
?
Measure whether outdoor terminal
voltage is normal
?
Restart the unit when the power supply
gets normal
Restart the unit when the power supply
gets normal
No
Yes
No
Reconnect it well
Reconnect it well
Yes
Measure whether the voltage
between L and N is normal
?
Measure whether the voltage
between L and N is normal
?
Yes
Measure whether input voltage of
bridge rectifier is normal
?
Measure whether input voltage of
bridge rectifier is normal
?
No
No
Check the wiring of
power wires well or
correctly
Check the wiring of
power wires well or
correctly
Reconnect it well
Reconnect it well
Check the wiring of L
and N well or correctly
Check the wiring of L
and N well or correctly
Reconnect it well
Reconnect it well
Check the wiring of
bridge rectifier well or
correctly
Check the wiring of
bridge rectifier well or
correctly
No
No
Yes
Replace the PFC module(If has)
Replace the PFC module(If has)
No
Measure whether the voltage
between P and N is normal
refer to the
Appendix
3
?
Measure whether the voltage
between P and N is normal
refer to the
Appendix
3
?
Replace the bridge rectifier
Replace the bridge rectifier
No
Check whether bridge
rectifier is normal
Check whether bridge
rectifier is normal
Check the wiring of reactor
or inductance
Check the wiring of reactor
or inductance
Reconnect the wiring
Reconnect the wiring
No
Check whether reactor or
inductance is normal
Check whether reactor or
inductance is normal
Yes
Replace reactor or
inductance
Replace reactor or
inductance
No
Check whether the connecting
wire between main board and the
IPM board is connected tightly
Check whether the connecting
wire between main board and the
IPM board is connected tightly
Reconnect it well
Reconnect it well
No
Check if the outdoor unit
ventilation is good
Check if the outdoor unit
ventilation is good
Yes
Make the outdoor unit ventilate well
Make the outdoor unit ventilate well
Check whether the refrigerant system is ok
Check whether the refrigerant system is ok
No
Check if the outdoor fan runs
properly
Check if the outdoor fan runs
properly
please refer to the solution of fan speed
has been out of control malfunction .
Find out the cause and have it solved.
please refer to the solution of fan speed
has been out of control malfunction .
Find out the cause and have it solved.
No
Yes
No
Yes
Yes
Check the compress is
normal
Check the compress is
normal
Yes
Replace the compressor
Replace the compressor
No
Replace IPM board
Replace IPM board
Replace the outdoor main PCB
Replace the outdoor main PCB
No
Check whether the connecting
wire of the compressor is
connected correctly or tightly
Check whether the connecting
wire of the compressor is
connected correctly or tightly
Reconnect it well
Reconnect it well
No
Yes
Yes
P0
Summary of Contents for MUCR-H6 Series
Page 15: ...Air Velocity Distributions Reference Data Indoor Units 13 30 42K Cooling Heating ...
Page 16: ...Air Velocity Distributions Reference Data 14 Indoor Units 48 60K Cooling Heating ...
Page 21: ...Field Wiring Indoor Units 19 10 Field Wiring ...
Page 30: ...Static Pressure 28 Indoor Units 5 Static Pressure MUCR 12 H6 MUCR 18 H6 ...
Page 31: ...Static Pressure Indoor Units 29 MUCR 24 H6 MUCR 30 H6 ...
Page 32: ...Static Pressure 30 Indoor Units MUCR 36 H6 MUCR 42 H6 MUCR 48 H6 MUCR 48 H6T MUCR 60 H6T ...
Page 41: ...Service Space Indoor Units 39 3 Service Space ...
Page 52: ...50 Indoor Units 10 Field Wiring ...
Page 61: ...Field Wiring Indoor Units 59 10 Field Wiring MUCSR 12 H6 MUCSR 18 H6 ...
Page 64: ...Dimensions 62 Outdoor Units Model Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Page 95: ...Refrigerant pipe installation Installation 93 ...