Troubleshooting
Electrical Control System
123
2.4.3 For the unit with TWINS function (For cassette, duct and ceiling floor).
2.4.3.1 Communication
malfunction
between master unit and indoor unit
F3 Displayed
F3 Displayed
Communication failure between
master unit and slave unit
Communication failure between
master unit and slave unit
Check the dial switch settings of
master unit and slave unit, is it right?
Check the dial switch settings of
master unit and slave unit, is it right?
Correct the
settings
Correct the
settings
No
Check the PQE communication wires
connection, is it good enough?
Check the PQE communication wires
connection, is it good enough?
Yes
Correct the wire
connections
Correct the wire
connections
No
One of the 2 indoor PCBs is defective.
Connect only one indoor unit to the outdoor
unit separately. The one caused E1 error code
is defective
One of the 2 indoor PCBs is defective.
Connect only one indoor unit to the outdoor
unit separately. The one caused E1 error code
is defective
Yes
2.4.3.2 Other malfunction between master unit and indoor unit
One indoor unit displays
”
E9
”
, which means another indoor unit is faulty. Check another indoor unit
’
s error
code and then follow the appropriate solutions to solve the malfunction.
E8
Summary of Contents for MUCR-H6 Series
Page 15: ...Air Velocity Distributions Reference Data Indoor Units 13 30 42K Cooling Heating ...
Page 16: ...Air Velocity Distributions Reference Data 14 Indoor Units 48 60K Cooling Heating ...
Page 21: ...Field Wiring Indoor Units 19 10 Field Wiring ...
Page 30: ...Static Pressure 28 Indoor Units 5 Static Pressure MUCR 12 H6 MUCR 18 H6 ...
Page 31: ...Static Pressure Indoor Units 29 MUCR 24 H6 MUCR 30 H6 ...
Page 32: ...Static Pressure 30 Indoor Units MUCR 36 H6 MUCR 42 H6 MUCR 48 H6 MUCR 48 H6T MUCR 60 H6T ...
Page 41: ...Service Space Indoor Units 39 3 Service Space ...
Page 52: ...50 Indoor Units 10 Field Wiring ...
Page 61: ...Field Wiring Indoor Units 59 10 Field Wiring MUCSR 12 H6 MUCSR 18 H6 ...
Page 64: ...Dimensions 62 Outdoor Units Model Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Page 95: ...Refrigerant pipe installation Installation 93 ...