Electrical Control Function
104
Electrical Control System
1. Electrical Control Function
1.1 Definition
T1: Indoor room temperature
T2: Coil temperature of indoor heat exchanger middle
T2B: Coil temperature of indoor heat exchanger outlet
T3: Coil temperature of condenser
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
1.2 Main Protection
1.2.1 Time delay at restart for compressor.
1.2.2 Temperature protection of compressor discharge
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
12K 18~60K
T5
Compressor off
Frequency limit1
F
E
D
C
Frequencies increase slowly
B
Normal
A
Frequency holding
Frequency limit2
T5
Compressor off
Frequency limit
Normal
Frequency holding
1.2.3 Sensor protection at open circuit and breaking disconnection.
1.2.5 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 7s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
1.2.6 Fan speed is out of control
For console:
When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display
the failure.
For other models:
When indoor fan speed keeps too low (lower than 300 RPM) for 50s, the indoor fan will shut off and restart
30s later, if protection happened 3 times when fan motor restart continuously, the unit will stop and the LED
will display the failure.
Summary of Contents for MUCR-H6 Series
Page 15: ...Air Velocity Distributions Reference Data Indoor Units 13 30 42K Cooling Heating ...
Page 16: ...Air Velocity Distributions Reference Data 14 Indoor Units 48 60K Cooling Heating ...
Page 21: ...Field Wiring Indoor Units 19 10 Field Wiring ...
Page 30: ...Static Pressure 28 Indoor Units 5 Static Pressure MUCR 12 H6 MUCR 18 H6 ...
Page 31: ...Static Pressure Indoor Units 29 MUCR 24 H6 MUCR 30 H6 ...
Page 32: ...Static Pressure 30 Indoor Units MUCR 36 H6 MUCR 42 H6 MUCR 48 H6 MUCR 48 H6T MUCR 60 H6T ...
Page 41: ...Service Space Indoor Units 39 3 Service Space ...
Page 52: ...50 Indoor Units 10 Field Wiring ...
Page 61: ...Field Wiring Indoor Units 59 10 Field Wiring MUCSR 12 H6 MUCSR 18 H6 ...
Page 64: ...Dimensions 62 Outdoor Units Model Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404 ...
Page 95: ...Refrigerant pipe installation Installation 93 ...