844 – AL HI T-Charge Air before EGR
Cause
Corrective action
The charge-air temperature at
sensor B9.1 has violated upper
limit value 1. Charge-air
temperature is too high.
1. Check sensor B9.1, replace as necessary.
2. Contact Service.
845 – AL HIHI T-Charge Air before EGR
Cause
Corrective action
The charge-air temperature at
sensor B9.1 has violated upper
limit value 2. Charge-air
temperature is too high.
1. Check sensor B9.1, replace as necessary.
2. Contact Service.
852 – AL Max. Blank Shot time expired
Cause
Corrective action
This alarm is generated when the
engine is at standstill if it was not
possible to relieve the pressure in
the HP accumulator within the set
time.
u
Contact Service.
956 – AL p5 ctrlvar limit min active
Cause
Corrective action
The charge-air pressure regulator
attempts to adjust its set value
but has reached its lower limit.
The bypass flap (M52) is fully
open.
u
Contact Service.
957 – AL p5 ctrlvar max BOI min active
Cause
Corrective action
Emission-related alarm. The
charge-air pressure regulator
attempts to adjust its set value
but has reached its upper limit.
The bypass flap (M52) is fully
closed. The retardation of the
start of injection (BOI) has
reached its maximum value.
1. Check air filter (plant side) for contamination.
2. Contact Service.
1024 – LOLO P-Fuel (Common RailA)
Cause
Corrective action
The HP fuel pressure at sensor
B48.1 has violated lower limit
value 2. Fuel pressure is too low.
u
Contact Service.
78 | Troubleshooting | MS15058/04E 2018-12