3 Technical Data
3.1 12V 4000 M63 engine data, EPA Tier 2, EU Stage IIIA, IMO
Tier II
Explanation:
DL Ref. value: Continuous power
BL Ref. value: Fuel stop power
A Design value
G Guaranteed value
R Guideline value
L Limit value up to which the engine can be operated without change, e.g. of power setting.
N Not yet defined value
- Not applicable
X Applicable
Heat exchanger
engine-mounted
Heat exchanger
remote
Application group
1A
1A
1A
1A
Intake air temperature
°C
25
45
25
45
Charge-air coolant temperature
°C
-
-
-
-
Raw water inlet temperature
°C
25
32
25
32
Barometric pressure
mbar
1000
1000
1000
1000
Site altitude above sea level
m
100
100
100
100
POWER-RELATED DATA (power ratings are net brake power as per ISO 3046)
Heat exchanger
engine-mounted
Heat exchanger
remote
Rated engine speed
A rpm
1800
1800
1800
1800
Fuel stop power ISO 3046
A kW
1500
1500
1500
1500
GENERAL CONDITIONS (for maximum power)
Heat exchanger
engine-mounted
Heat exchanger
remote
Intake depression (new filter)
A mbar
15
15
15
15
Intake depression, max.
L
mbar
30
30
30
30
MODEL RELATED DATA (basic design)
Heat exchanger
engine-mounted
Heat exchanger
remote
Cylinder arrangement: V angle
Degrees
(°)
90
90
90
90
Bore
mm
170
170
170
170
Stroke
mm
210
210
210
210
Cylinder displacement
Liters
4.77
4.77
4.77
4.77