153224 – HI Knock Integrator A4
Yellow alarm. Initiated by SAM.
Cause
Corrective action
Readjustment of ignition timing
beyond a limit value because
knocking was detected in this
cylinder.
1. Check emission values.
2. Check ignition timing (→ Page 137).
3. Check combustion chamber.
4. Check gas quality if feasible (methane number).
153225 – HI Knock Integrator A5
Yellow alarm. Initiated by SAM.
Cause
Corrective action
Readjustment of ignition timing
beyond a limit value because
knocking was detected in this
cylinder.
1. Check emission values.
2. Check ignition timing (→ Page 137).
3. Check combustion chamber.
4. Check gas quality if feasible (methane number).
153226 – HI Knock Integrator A6
Yellow alarm. Initiated by SAM.
Cause
Corrective action
Readjustment of ignition timing
beyond a limit value because
knocking was detected in this
cylinder.
1. Check emission values.
2. Check ignition timing (→ Page 137).
3. Check combustion chamber.
4. Check gas quality if feasible (methane number).
153227 – HI Knock Integrator A7
Yellow alarm. Initiated by SAM.
Cause
Corrective action
Readjustment of ignition timing
beyond a limit value because
knocking was detected in this
cylinder.
1. Check emission values.
2. Check ignition timing (→ Page 137).
3. Check combustion chamber.
4. Check gas quality if feasible (methane number).
153228 – HI Knock Integrator A8
Yellow alarm. Initiated by SAM.
Cause
Corrective action
Readjustment of ignition timing
beyond a limit value because
knocking was detected in this
cylinder.
1. Check emission values.
2. Check ignition timing (→ Page 137).
3. Check combustion chamber.
4. Check gas quality if feasible (methane number).
88 | Troubleshooting | MS150033/04E 2012-07
TIM-ID: 0000017543 - 001