091 – SS Release Speed Not Reached
ZKP-Number:
Red alarm. Start terminated.
Associated parameter 2.1090.924
Cause
Corrective action
The speed (starter
DISENGAGE) was not attained,
ignition not working or no gas
available.
1. Check ignition.
2. Check gas supply.
3. Check mixture setting.
092 – SS Starter Speed Not Reached
ZKP-Number:
Red alarm. Start terminated.
Associated parameter 2.1090.923
Cause
Corrective action
Minimum speed for flushing
process and ignition release was
not attained.
u
Check starter system.
093 – SS T-Preheat
ZKP-Number:
Red alarm. Engine shutdown.
Associated parameter 2.1090.922
Cause
Corrective action
Preheating temperature too low
(limit value 2). Coolant
temperature too low for engine
start.
1. Check preheating.
2. Check differential coolant pressure.
3. Check heating elements.
4. Check cabling.
094 – LO T-Preheat
ZKP-Number:
Yellow alarm.
Associated parameter 2.1090.921
Cause
Corrective action
Preheating temperature too low
(limit value 1). Coolant
temperature too low for engine
start.
1. Check preheating.
2. Check differential coolant pressure.
3. Check heating elements.
4. Check cabling.