020 – SS T-Exhaust A
ZKP-Number:
Yellow alarm.
Associated parameter 2.0126.932
Cause
Corrective action
Exhaust gas temperature (A
side) after turbine too high (limit
value 2). Incorrect ignition timing,
mixture too lean or too rich,
damage to turbine.
1. Check exhaust turbocharger.
2. Check ignition timing (→ Page 137).
3. Check mixture setting.
4. Check spark plugs.
021 – HI T-Exhaust B
ZKP-Number:
Yellow alarm.
Associated parameter 2.0127.931
Cause
Corrective action
Exhaust gas temperature (B
side) after turbine too high (limit
value 1). Incorrect ignition timing,
mixture too lean or too rich,
damage to turbine.
1. Check exhaust turbocharger.
2. Check ignition timing (→ Page 137).
3. Check mixture setting.
4. Check spark plugs.
022 – SS T-Exhaust B
ZKP-Number:
Yellow alarm.
Associated parameter 2.0127.932
Cause
Corrective action
Exhaust gas temperature (B
side) after turbine too high (limit
value 2). Incorrect ignition timing,
mixture too lean or too rich,
damage to turbine.
1. Check exhaust turbocharger.
2. Check ignition timing (→ Page 137).
3. Check mixture setting.
4. Check spark plugs.
025 – HI P-Diff-Lube Oil
ZKP-Number:
Yellow alarm.
Associated parameter 2.0154.931
Cause
Corrective action
Pressure loss via oil filter too
high (limit value 1).
1. Replace oil filter (→ Page 159).
2. If this fault message occurs again after unexpectedly short filter
runtime, check oil filter for deposits, change oil if required
(→ Page 157).