The status of the switching points is reported in parallel to the position
values or velocity values via the PROFINET protocol. A magnet must
be specified for each switching point, which is used to check the
respective limit. For a single position measurement with one magnet,
the same magnet is assigned to the high and the low limit. For a
multi-position measurement, you can assign different magnets on
the sensor to the high and the low limit. Fig. 46 shows an example
with three magnets. Magnet 1 is used to check the low limit, while the
magnet 3 is used to monitor the high limit. Magnet 2 has no influence
on the checking of the work area.
Fig. 46: Example of checking the switching points at R-Series
V
PROFINET with 3 magnets
Bit value
0
1
Stroke length
Low limit
High limit
Magnet 1
Magnet 2
Magnet 3
• Ignoring offsets configured in the project:
You can use the "Config
Flags 1" entry to set whether the sensor should accept or ignore
the offsets transmitted by the controller when establishing the
connection. You can adjust this in the module parameters of the
sensor in the "Config Flags" section (Fig. 47). You can set the
following values for bit 1 of the "Config Flags 1" entry:
• Value 0: The offsets configured in the project are accepted by
the sensor
• Value 1: The offsets configured in the project are ignored by the
sensor
The other bits of "Config Flags 1" as well as the entries "Config Flags 2"
and "Config Flags 3" have no influence on the MTS profile.
Fig. 47: Config Flags – MTS profile