must be returned to the factory for modification.
DP power supplies are optionally available to operate on 380 V or 480 V, 3ö, 50 to 400 Hz
mains. For conversion from 380 V to 415 V or from 480 V to 440 V operation, two internal
wiring changes must be made to each power module. The locations are not accessible to the user
and the power supply must be returned to the factory for modification.
1.5
Specifications
The following specifications describe the published operational characteristics of the DP Series
power supplies.
Input voltage:
208 Vac (operating range 187 - 229 Vac), 50-400 Hz, 1ö;
240 Vac (operating range 216 - 264 Vac), 50-400 Hz, 1ö;
208 Vac (operating range 187 - 229 Vac), 50-400 Hz, 3ö;
240 Vac (operating range 216 - 264 Vac), 50-400 Hz, 3ö;
380 Vac (operating range 342 - 418 Vac), 50-400 Hz, 3ö;
415 Vac (operating range 373 - 456 Vac), 50-400 Hz, 3ö;
440 Vac (operating range 396 - 484 Vac), 50-400 Hz, 3ö;
480 Vac (operating range 432 - 528 Vac), 50-400 Hz, 3ö.
Line regulation:
Voltage Mode: ±.004% of full scale,
Current Mode: ±.02% of full scale.
Load regulation:
Voltage Mode: ±.01% of full scale,
Current Mode: ±.04% of full scale.
Stability:
0.10 % for 8 hours after 30 minute warm up.
Load transient response:
2 ms to recover within ±1% of regulated output with a 50% to 100% or 100% to 50% step load
change.
Maximum Slew Rate:
100 ms for an output voltage change from 0 to 63%,
100 ms for an output current change from 0 to 63%.
Efficiency:
greater than 86%, see Model and Ratings tables for details.
Temperature coefficient:
0.04 %/
E
C of maximum output current.
5
Summary of Contents for DP SERIES II
Page 1: ...OPERATING AND SERVICE MANUAL DP SERIES II DC POWER SUPPLIES...
Page 2: ......
Page 3: ...MAGNA POWER ELECTRONICS INC 39 ROYAL ROAD FLEMINGTON NJ 08822 January 6 2010...
Page 4: ......
Page 6: ...improper use of the equipment and accessories ii...
Page 28: ...Figure 1 2 DP Series air cooled 10 kW to 30 kW package drawing with D Version front panel 15...
Page 47: ...Figure 3 7 Set remote sense Figure 3 8 Set internal control 34...
Page 48: ...Figure 3 9 Set external control Figure 3 10 Set rotary input 35...
Page 49: ...Figure 3 11 Set keypad input Figure 3 12 Set external program input 36...
Page 50: ...Figure 3 13 Set remote input Figure 3 14 Set external interlock 37...
Page 53: ...Figure 3 15 Calibration 40...
Page 61: ...Figure 3 24 Calibration 48...
Page 63: ...Figure 3 25 a Local and b remote sensing 50...
Page 64: ...Figure 3 26 External a resistive b voltage and current programming 51...
Page 111: ...98...
Page 113: ...Figure 5 1 Configuration setup Figure 5 2 GPIB communications setup 100...
Page 118: ...Figure 5 7 Register Panel Figure 5 8 Calibration Panel 105...
Page 119: ...Figure 5 9 Firmware Panel Figure 5 10 Modulation Panel for Version D models only 106...
Page 121: ...Figure 6 1 Block diagram 108...
Page 139: ...Figure B 1 Information Panel Figure B 2 Configure Panel 126...
Page 140: ...Figure B 3 Reboot in Progress Panel Figure B 4 Web Control Panel 127...
Page 145: ...Figure D 1 RS485 a 2 wire and b 4 wire connections 132...