MM64003a_e.doc / Feb-09
Page 30 / 44
6.2.9.
Characteristics and functions of the Control Inputs
F08
Range
Default
F08.109 Input 1 Configuration
0 … 7
0
0= NPN (switch to -), function active LOW
1= NPN (switch to -), function active HIGH
2= NPN (switch to -), rising edge
3= NPN (switch to -), falling edge
4= PNP (switch to +), function active LOW
5= PNP (switch to +), function active HIGH
6= PNP (switch to +), rising edge
7= PNP (switch to +), falling edge
F08.110 Input 1 Action
0 … 15
0
0=
No
function
1= Reset counter 1 (encoder 1)
2= Reset counter 2 (encoder 2)
3=
Reset
difference
[
counter1 - counter2]
4=
Scroll
Display
5=
n.
a.
6=
Keyboard
Disable
7=
Store
EEProm
8=
Release
Function
Lock
9=
Freeze
Function
For more details about these
functions see section 7.
F08.111 Input 2 Configuration
See „Input 1“ (F08.109)
F08.112 Input 2 Action
See „Input 1“ (F08.110)
F08.113 Input 3 Configuration
See „Input 1“ (F08.109)
F08.114 Input 3 Action
See „Input 1“ (F08.110)
F08.115 Input 4 Configuration
0 – 3
0= NPN (switch to -) function active LOW
1= NPN (switch to -) function active HIGH
2= PNP (switch to +), function active LOW
3= PNP (switch to +), function active HIGH
no edge-triggered functions are
possible with Input 4
F08.116 Input 4 Action
See „Input 1“ (F08.110)
•
Unconnected NPN inputs are always HIGH (internal pull-up resistor)
Unconnected PNP inputs are always LOW (internal pull-down resistor)
n.a. = not applicable
Summary of Contents for MM 640