3 Controller
Parallel I/O unit 3-69
Table 3-22 : Electrical specifications of input circuits
Table 3-23 : Electrical specifications for the output circuits
The output circuit protective fuses prevent failure in case of load short-circuit and
improper connections. Please do not connect loads that cause the current to exceed
the maximum rated current. If the maximum rated current is exceeded, the internal
transistors may be damaged.
Item
Specification
Internal circuit
Type
DC input
<Sink type>
<Source type>
Number of input points
32
Insulation method
Photo coupler insulation
Rated input voltage
12VDC/24VDC
Rated input current
Approx 3mA/7mA
Working voltage range
10.2 to 26.4VDC(Ripple factor should be less than 5%.)
ON voltage/ON current
8VDC or more/ 2mA or more
OFF voltage/ OFF current
4VDC or less/ 1mA or less
Input resistance
Approx. 3.3kΩ
Response time
OFF-ON
10ms or less (24VDC)
ON-OFF
10ms or less (24VDC)
Common method
8 points per common
External cable connection method Connector
Item
Specification
Internal circuit
Type
Transistor output
<Sink type>
<Source type>
No. of output points
32
Insulation method
Photo-coupler insulation
Rated load voltage
12VDC/24VDC
Rated load voltage range
10.2 to 30VDC(peak voltage 30VDC)
Max. load current
0.1A/point (100%)
Leakage current at OFF
0.1mA or less
Max. voltage drop at ON
0.9VDC(TYP.)
Response time
OFF-ON
2ms or less
(hardware response time)
ON-OFF
2ms or less
(Resistance load) (hardware response time)
Fuse rating
Fuse 3.2A (one per common) Replacement not possible
Common method
8 points per common (common terminal: 8 points)
External wire connection
method
Connector
External power
supply
Voltage
12VDC/24VDC(10.2 to 30VDC)
Current
60mA (TYP. 24VDC per common) (base drive current)
3.3K
Input
820
24V/12V
(COM)
3.3K
Input
820
0V(COM)
(24/12V)
Outline
(0V)
Fuse
Fuse (24/12V)
Outline
(0V)
CAUTION