4
- 1
4.1 MODBUS(R) Standard Function Support List
4
MODBUS(R) STANDARD FUNCTIONS
CHAPTER4 MODBUS(R) STANDARD FUNCTIONS
This chapter explains the MODBUS standard functions supported by the QJ71MB91.
Using the MODBUS standard functions allows you to read/write to programmable
controller CPU devices and to load the QJ71MB91 status into the master.
4.1 MODBUS(R) Standard Function Support List
(1) MODBUS standard function support list
The following table indicates a list of the MODBUS standard functions supported by
the QJ71MB91.
(Continued on next page)
Table4.1 MODBUS
standard function support list
Function
code
(Sub code)
Sub-function
code
Function
Description
Accessible
devices
per
message
Broadcast Reference
01
-
Read coils
Reads the status (ON/OFF) of one or
more coils.
1 to
2000 points
02
-
Read discrete inputs
Reads the status (ON/OFF) of one or
more inputs.
1 to
2000 points
03
-
Read holding registers
Reads the values of one or more
holding registers.
1 to
125 points
04
-
Read input registers
Reads the values of one or more input
registers.
1 to
125 points
05
-
Write single coil
Writes a value (ON/OFF) to one coil.
1 point
06
-
Write single register
Writes a value to one holding register.
1 point
07
-
Read exception status
Reads error status.
-