2) When not using GX Configurator-MB
The automatic communication function buffer area data in the QJ71MB91 are
transferred to the programmable controller CPU on the MELSECNET/H
remote master station with the REMTO/REMFR instruction.
I/O signals are transferred by MELSECNET/H link refresh and MELSECNET/
H link scan.
Figure 9.27 Communications (When not using GX Configurator-MB)
* 1 Set the MELSECNET/H link refresh by refresh parameters in the network parameters.
(
* 2 Set the MELSECNET/H link scan by the network range assignment in the network parameters.
(
* 3 Automatic communication parameters are set from sequence program. (
* 4 The automatic communication function buffer area data in the QJ71MB91 are transferred to the
programmable controller CPU on the MELSECNET/H remote master station with the REMTO/
REMFR instruction. (
400001
400100
000001
015001
016024
065536
465536
MELSECNET/H remote master station
MELSECNET/H remote I/O station (setting target)
MELSECNET/H
remote I/O module
Device
CH2 Automatic communication
function buffer input area
CH2 Automatic
communication
function buffer
output area
QJ71MB91
Programmable
controller CPU
Device
MELSECNET/H
link refresh*1
MELSECNET/H link scan*2
MELSECNET/H
remote master module
2000
H
2100
H
213F
H
2FFF
H
64 words
100 words
Holding register
Coil
4000
H
4A00
H
4A63
H
4FFF
H
*4
*3
*3
MODBUS slave device
(station No.1)
R
MODBUS slave device
(station No.2)
R