7
- 5
7.2 Automatic Communication Parameter
7.2.1 Automatic communication parameter details
7
PARAMETER SETTING
(1) Setting parameter existence
Set whether to enable or disable the automatic communication parameters.
(2) Target station No.
Specify a slave to which request messages are sent.
The target station No. is entered in the address field of the request message sent to
the communication target slave device.(
(3) Request interval timer value
The Request interval timer represents the interval between any successive request
message transmissions in the automatic communication function.
The time from when the QJ71MB91 sends a request message until it sends the next
request message is measured.
Table7.1 Automatic communication parameter list (Continued)
Address
Parameter name
Setting range
Default
Reference
CH1
CH2
0207
H
(519)
0387
H
(903)
Automatic
communication
Parameter 1
Read
Setting
Target MODBUS
device head number
0 to 65535
0
0208
H
(520)
0388
H
(904)
Access points
0 to 2000
0
0209
H
(521)
0389
H
(905)
Write
setting
Head buffer memory
address
0000
H
: None
3000
H
to 3FFF
H
:
CH1 write data storage area
4000
H
to 4FFF
H
:
CH2 write data storage area
0000
H
020A
H
(522)
038A
H
(906)
Target MODBUS
device head number
0 to 65535
0
020B
H
(523)
038B
H
(907)
Access points
0 to 1968
0
020C
H
to
037F
H
(524 to
895)
038C
H
to
04FF
H
(896 to
1279)
Automatic
communication
Parameter 2 to
32
(Same as in automatic communication parameter 1)
Figure 7.2 Request interval timer
Request interval timer
Master
(QJ71MB91)
Slave
Request
message
Receiving
response
message
Request
message
Receiving
response
message
Response
Message
Request
message
processing
Response
Message
Request
message
processing
Summary of Contents for QJ71MB91
Page 1: ......
Page 2: ......
Page 366: ...App 14 Appendix 4 External Dimensions APPENDICES Memo ...
Page 371: ......
Page 372: ......